M
SG32-UG-EN-V01 Dec 2016
2
Surge Impulse (Voltage Impulse)
Ranges
Two (2)
Impulse voltage
0 to 16 kV
0 to 32 kV
Impulse Energy @ 100% of range
1500 joule @ 0 to 16 kV
1500 joule @ 0 to 32 kV
Impulse Repetition Rate
Single Shot
1 to 15 seconds
Arc Reflection & Arc Reflection (Multi-shot) Prelocating
Voltage
0 to
16 kV
0 to
32 kV
Energy @ 100% of range
1500 joule @
0 to
16 kV
1500 joule @
0 to
32 kV
Number of Traces (Multi-shot):
1024 to 16
(Dependent on range selected)
ICE / Surge Pulse / Current Decoupling / Impulse Current Prelocating
Voltage
0 to
16 kV /
0 to
32 kV
Energy @ 100% of range
1500 joule @
0 to
16 kV
1500 joule @
0 to
32 kV