SPECIFICATIONS
SG32-UG-EN-V01 Dec 2016
3
LOW VOLTAGE
MTDR 100 (Time Domain Reflectometer, built into lid)
Operation
Single Jog-Dial
Modes
Pulse Echo, Direct, Comparison,
Arc Reflection, Arc Reflection Multi-shot,
Differential Arc Reflection (DART) Impulse Current
Ranges
10 ranges:
100 m to 55 km ; 328 ft to 180,445 ft
Pulse Width
50 ns, 100 ns, 200 ns, 500 ns, 1
μ
s, 2
μ
s, 5
μ
s, 10
μ
s
Pulse Amplitude
25V into 50 Ohms
Sampling Rate
100 MHz
Resolution (VP=55%)
0.82 m / 2.7 ft
Time base accuracy
200 ppm
Output impedance
50 Ohms
Gain
Variable over 60 dB in 5 dB steps
Display
XGA 1024 x 768 : 26.5 mm (10.4”)
Storage
On-board and USB
Metering
Voltmeter
Analog 0 to 40 kV / Accuracy 5%
Ammeter
Analog 0 to 75 mA / Accuracy 5%
Environmental
Operating Temp
-0 to 50
o
C / 32 to 120
o
F
Storage Temperature
-20 to 55
o
C / -4 to 131
o
F
Humidity
5 to 95% RH non-condensing (operating)
Elevation
Maximum 1600 m (De-rate voltages at higher altitudes)
Содержание SG32-1500M
Страница 2: ......
Страница 3: ...SG32 1500M Megger Portable Cable Fault Locator...
Страница 6: ......
Страница 16: ...M SG32 UG EN V01 Dec 2016 6 M...
Страница 26: ...M SG32 UG EN V01 Dec 2016 16 M...
Страница 30: ...M SG32 UG EN V01 Dec 2016 20 M...
Страница 47: ...SG32 UG EN V01 Dec 2016 37 ADDENDUM 1 Cable Fault Location Applications Guide...
Страница 55: ...SG32 UG EN V01 Dec 2016 45 ADDENDUM 3 MTDR100 User Guide...
Страница 56: ...M SG32 UG EN V01 Dec 2016 46 M...
Страница 75: ...SG32 UG EN V01 Dec 2016 65 Megger Quality System Certificate...
Страница 76: ...M SG32 UG EN V01 Dec 2016 66 M...