M
SG32-UG-EN-V01 Dec 2016
64
NOTE: If the Cable length is known, then Velocity can be verified. Place the left
cursor at the start of the cable and the right cursor at the Cable end and
adjust the Velocity. When the Distance shown for the right cursor
matches the known Cable length, the velocity is set to its correct value.
Test: Select by depressing jog-dial.
When activated, turns the MTDR into real-
time pulse echo mode, with continuous
sampling mode.
Real-time / continuous sampling is
cancelled by depressing jog-dial.
TRIGGER ON:
Select by depressing jog-
dial.
Required in: Arc Reflection; Surge Impulse;
Loop off / Loop on; modes to
arm or
initiate
the transient memory required for
these methods. The following message to
show that the TDR is waiting for a trigger
will be displayed at the top centre of the
TDR screen.
NOTE:
You will be unable to capture any traces with the above methods unless you
ARM
the transient memory function first.
CANCEL:
Selected by depressing jog-dial.
Cursors: S
elect by depressing jog-dial.
Allows the operator to move the “right” or
“left” cursor. Active cursor will appear as a
“dotted” line on the TDR display.
NOTE: If Cursor Offset is active, only the Right
Cursor can be selected.
C A N C E L
TRIGGER ON
LIVE TRACE
Содержание SG32-1500M
Страница 2: ......
Страница 3: ...SG32 1500M Megger Portable Cable Fault Locator...
Страница 6: ......
Страница 16: ...M SG32 UG EN V01 Dec 2016 6 M...
Страница 26: ...M SG32 UG EN V01 Dec 2016 16 M...
Страница 30: ...M SG32 UG EN V01 Dec 2016 20 M...
Страница 47: ...SG32 UG EN V01 Dec 2016 37 ADDENDUM 1 Cable Fault Location Applications Guide...
Страница 55: ...SG32 UG EN V01 Dec 2016 45 ADDENDUM 3 MTDR100 User Guide...
Страница 56: ...M SG32 UG EN V01 Dec 2016 46 M...
Страница 75: ...SG32 UG EN V01 Dec 2016 65 Megger Quality System Certificate...
Страница 76: ...M SG32 UG EN V01 Dec 2016 66 M...