PPX40 Configuration
PPX40 Internal Leads Configuration
One orange output cable, with insulated jacket rated at 60 kV DC, appropriately marked.
Three black ground cables with insulated jacket rated at 60 kV DC, appropriately marked.
One black ground cable with braided jacket, appropriately marked.
Table 7:
Baker PPX40 HiPot and Surge internal connections.
Lead 1 Orange
Lead 2 Black
Lead 3 Black
Lead 4 Black
Black Braid
High Voltage
Ground
Ground
Ground
Ground
PPX40 Configuration for DC HiPot Tests—Single-Phase Test Leads
1. Connect test lead 4 to ground (motor frame) and test lead 1 to the winding phase connection you want to test.
2. Leave test leads 2 and 3 disconnected/open.
3. Connect the safety ground to the station/earth ground.
Table 8:
Baker PPX40 device under test connections for HiPot testing.
Lead 1 Orange
(Energized)
Lead 2 Black
(Ground)
Lead 3 Black
(Ground)
Lead 4 Black
(Ground)
Black Braid
(Ground)
Motor phase A
Not connected
Not connected
Motor frame
Station/earth ground
PPX40 Configuration for Surge Tests—Single-Phase Test Leads
The PPX40 does not have a Test Select switch. When using the Baker PPX40 for single-phase testing of three-phase
windings, you must manually move the orange lead (energized during test) to test each motor phase in turn as
shown in the table below.
Table 9:
Baker PPX40 device under test connections for Surge testing.
Surge
Motor
Phase
Lead 1 Orange
(Energized)
Lead 2 Black
(Ground)
Lead 3 Black
(Ground)
Lead 4 Black
(Ground)
Black Braid
(Ground)
A
Motor phase A
Motor phase B
Motor phase C
Motor frame
Station/earth
ground
B
Motor phase B
Motor phase A
Motor phase C
C
Motor phase C
Motor phase B
Motor phase A
1. Power up both the tester and the power pack.
2. Check that the open ground detect warning banner does not appear in the Baker DX Display Area, or that the
open ground detection light on the Baker AWA is not illuminated.
Baker Power Pack Introduction
14
Baker Power Packs User Guide 71-061RC EN V2
www.megger.com
Содержание PPX30
Страница 1: ...Baker Power Packs PPX30 PPX30A PPX40 User Guide...
Страница 2: ......
Страница 6: ...Notices iv Baker Power Packs User Guide 71 061RC EN V2 www megger com...
Страница 12: ...Baker Power Pack Introduction 4 Baker Power Packs User Guide 71 061RC EN V2 www megger com...
Страница 24: ...Baker Power Pack Setup 16 Baker Power Packs User Guide 71 061RC EN V2 www megger com...
Страница 28: ...Using Power Packs with Baker AWA Testers 20 Baker Power Packs User Guide 71 061RC EN V2 www megger com...
Страница 74: ...66 Baker Power Packs User Guide 71 061RC EN V2 www megger com...
Страница 78: ...70 Baker Power Packs User Guide 71 061RC EN V2 www megger com...
Страница 82: ...74 Baker Power Packs User Guide 71 061RC EN V2 www megger com...