VIEW SAVED DATA. Pressing WYE MAX HOLD or DELTA MAX HOLD
will display the desired three-phase MAX HOLD screen. The same single-
phase feature applies to the three phase MAX HOLD function.
4.6
THREE-PHASE
OPERATION
NOTE:
Due to the sensitivity of the Power Multimeter to very low levels of
voltage and current, it is highly recommended that the protective
ground terminal be connected to an earth ground and jumpered to
the voltage input neutral post before making any measurements!!!!
This is recommended even if the AC power cord is used.
The three-phase operation mode is intended for measuring all 3-phase quantities
in a wye or delta installation. Note:
Lag
; displayed phase angles lags the
reference in the Lag mode.
Lead
;displayed phase angles leads the reference in
the Lead mode.
NOTE: Instrument defaults to VAN as the phase reference. If current
only is to be measured, the phase reference must be changed to
IA, IB or IC.
Three phase watts are displayed in the three watt method.
4.6.1
SELECTING
THE
CONFIGURATION
From
the
Main Menu, select the
THREE PHASE WYE
or
THREE PHASE
DELTA
configuration by pressing the corresponding function key. The
instrument will immediately go into the measuring screen.