Electrical Installation
The IonWash™ is designed for use with a range of supply voltages
Voltages higher than 235V 3-Phase (Phase-Phase)
For installations where the 3-Phase supply voltage is higher than 235V (phase to phase) the IonWash™ must be
run with a neutral supply to ensure that the blowers do not fail beyond repair. If a neutral supply is not available
an additional transformer will be required, the spec of this transformer is under the section ‘Electrical Delta-Star
Transformer’.
For this voltage, the wiring inside the IonWash™ will be pre-set by Meech in ‘Star’ configuration which ensures that
the neutral connection is connected to the pumps internally. See Wiring diagrams at the rear of this manual for the
diagram showing the ‘Star’ configuration IonWash™ internal wiring.
Voltages lower than 235V 3-Phase (Phase-Phase)
For installations where the 3-Phase supply voltage is below 235V (phase to phase) a neutral supply is optional
providing that the IonWash™ has been pre-set by Meech in ‘Delta’ configuration.
For this voltage, the wiring inside the IonWash™ will be pre-set by Meech in ‘Delta’ configuration which enables the
IonWash™ to run without a neutral. See wiring diagrams at the rear of this manual for diagram showing the ‘Delta’
configuration IonWash™ internal wiring.
It is critical that the IonWash™ is run with the correct wiring configuration to match the supply voltage – if not this
will result in the pumps failing beyond repair.