17
1
2
3
4,6,8,10
11,12
13,14
5
15,16
17,18
7
9
Remote
ON-OFF
+5V-AUX
T-ALARM
GND-AUX
Fan Fail
+12V-AUX
GND-AUX
DC OK
AC OK
SCL
SDA
CANL
CANH
DATA-
DATA+
The unit can turn the output ON/OFF by dry contact between
Remote ON/OFF and +5-AUX.(Note)
Short (4.5 ~ 5.5V) : Power ON ; Open(0 ~ 0.5V) : Power OFF ;
The maximum input voltage is 5.5V
High (3.5 ~ 5.5V) : When the internal temperature exceeds
the limit of temperature alarm.
Low (-0.5 ~ 0.5V) : When the internal temperature is normal.
The maximum sourcing current is 10mA and only for output.(Note)
The maximum sourcing current is 10mA and only for output.(Note)
The maximum sourcing current is 10mA and only for output.(Note)
The maximum sourcing current is 10mA and only for output.(Note)
Auxiliary voltage output, 4.5~5.5V, referenced to GND-AUX
(pin 4,6,8,10,17,18) only for Remote ON/OFF used. This output
is not controlled by the Remote ON/OFF control.
High(3.5~5.5V):When the fan fail.
Low(-0.5~0.5V):When the fan works normally.
High(3.5 ~ 5.5V) : When Vout 80% 6%.
≦
±
Low(-0.5 ~ 0.5V) : When Vout 80% 6%
≧
±
.
High (3.5 ~ 5.5V): When AC input 335 1.5%Vac, PSU works normally.
≧
±
Low (-0.5 ~ 0.5V): When AC input 320 1.5%Vac, PSU shut down.
≦
±
Auxiliary voltage output GND.
The signal return is isolated from the output terminals (+V & -V).
For PMBus model: Serial Clock used in the PMBus interface.(Note)
For PMBus model: Serial Clock used in the PMBus interface.(Note)
For CANBus model: Data line used in CANBus interface.(Note)
For CANBus model: Data line used in CANBus interface.(Note)
For MODBus model: Data line used in MODBus interface.(Note)
For MODBus model: Data line used in MODBus interface.(Note)
Auxiliary voltage output, 11.4~12.6V, referenced to
GND-AUX (pin17 & 18).
The maximum load current is 1A. This output is not controlled
by “Remote ON-OFF”.
Auxiliary voltage output GND.
The signal return is isolated from the output terV & -V).
Note: Isolated signal, referenced to (GND-AUX).
Pin No.
Function
Description
4
18
4.2 L type
4. .1
2
Panel Description
DIP-SW1:
SVRs:
DIP-SW81:
A
A
C D
E
G
F
B
B
C
D
E
F
G
AC input terminals
DC output terminals
Used for parallel control/PV/PC functions
Function pins:
They are used for control and monitoring functions. Please refer
to 4. .2 and 4. .3.
2
2
LED indictor:
Indicate the status of the supply and load condition.
Used to adjust output voltage. The one on the top for fine-tune,
the other for coarse-tune.
Position 4 is an internal termination resistor that prevents signal
rebound for differential signals of CAN bus and Modbus.
Position 1~3 are for device addressing when using communication
interface.
4