23
5.3.3
Communication
Output voltage can be adjusted through communication interfaces:
PMBus, CAN bus or Modbus. Please refer to chapter 6 for detailed
information.
5.4
Output Current Adjustment
●
Output current can be adjusted via PC and communication interface.
A.
Overload Protection(OLP) value
Default setting is at
5.4.1 PC(Output Current Programming)
ON
OFF
1 2 3
ON
OFF
1 2 3
B. To enable Constant Current Level Programming, have the DIP
switch position-2 set as
C Connect output of the external DC source to PC+ and
, as
.
-V(signal)
shown in Figure 5-4.
D.Relationship between output current and external DC source I
shown in Figure 5-5.
E.Covered by over temperature protection, auto de-rating function
works under operation either in PC mode or under control by
communication protocol.
T1(Typ.):
Maximum ambient temperature of full load
T2(Typ.): T1+5℃
Figure
5 4
-
DIP SW1
LOAD
+V
-V
PIN1,2 -V(Signal)
EXTERNAL VOLTAGE (DC)(0~5V)
PIN5,6 PC+
5
24
Figure
5 5
-
Non-Linear
(
)
HORIZONTAL
T
1
T
2
20
40
50
60
80
100
AMBIENT TEMPERATURE ( )
℃
LOAD
(%)
20
OUTPUT
CURRENT(%)
100
110
Iout
0
EXTERNAL VOLTAGE (DC)
1
4.7
V
4.8
Non-Linear
5.5
Parallel function
5 5
. .1
DA, DB signal and parallel control function
(1)
Non-parallel operation
A.
Set the DIP switch of postion-1 as
B.
By default, non-parallel operation
B.
PSUs are configured in parallel operation
(2)
Default Parallel operation
A.
Set the DIP switch of postion-1 as
ON
OFF
1 2 3
ON
OFF
1 2 3
DIP SW1
Figure
5 6
-
5
◎
The 100% output current is 150/87/46.3/30A.