11
B.Recommended settings for cooling water operating parameters.
Ambient temperature: 50℃
Inlet temperature: 5~15℃
Flow rate (minimum): 4~ 10LPM
Humidity: 20~90% RH non-condensing
Pressure drop 6 psi (minimum), pressure inlet 80 psi (maximum)
C.Condensation - Safe operating area.
3.1.3
With 85CFM forced air
L type with a 85CFM forced air fan for heat dissipation, it is suggested
mounting on horizontal surfaces as below.
Air flow
direction
100mm
FAN
85CFM x 2
Ambient
t
e
mp
(
)
℃
0
10
15
20
30
40
50
60
0
10
20
30
40
50
60
70
80
90
100
45
40
38
35
30
25
20
15
Condensation-safe operating area
Electric room relative humidity %
coolant
temp
℃
safe
operating
area
3
12
3.2
Installation Notes
A.Before any installation or maintenance work, please disconnect your
system from the utility. Ensure that it cannot be re-connected
inadvertently.
B.Keep enough insulation distance between mounting screws and
internal components of power supplies. Please refer to 2.5 Mechanical
specification to receive the maximum length of mounting screw
C.Mounting methods other than chapter 3.1 or operate under high
a m b i e n t t e m p e r a t u r e m a y i n c r e a s e t h e i n t e r n a l c o m p o n e n t
temperature and will require a de-rating in output current.
D.Fans and ventilation holes must be kept free from any obstructions. Also
a 10-15 cm clearance must be kept when the adjacent device is a heat
source.
Cable connections should be as short as possible and make sure that
suitable cables are chosen based on safety requirement and rating of
current. Small cross section will result in lower efficiency, less output
power and the cables may also become overheated and cause danger. For
selection, please refer to table 3-1.
3 3
.
Cable Size Selection
6A
6-10A
10-16A 16-25A 25-32A 32-40A 40-63A 63-80A 80-100A
0.75
1.00
1.5
2.5
4
6
10
16
25
Suggest current
(Amp)
Cross-section of
lead
(mm )
2
Note: Current each wire carries should be de-rated to 80% of the current
Make sure that all strands of each stranded wire enter the terminal connection and the screw
terminals are securely fixed to prevent poor contact.
AWG
18
16
14
12
10
8
6
4
2
Table 3-1 cable recommendations
3