![McQuay ACZ 045A Скачать руководство пользователя страница 85](http://html1.mh-extra.com/html/mcquay/acz-045a/acz-045a_installation-operation-and-maintenance-manual_1756090085.webp)
IOMM ACZ/AGZ-1
85
Table 41, MENU 15 SoftLoad Spts
Screen
Display
Factory Setpoint
Range
1
Time Left= xxmin
2
SoftLoad= xx min
20
0 - 254
3
SoftLdMaxStg= x
4
1 - 4
4
LoadDelay= xxsec
15
0 - 254
Table 42, MENU 16 CompressorSpt
Screen
Display
Factory Setpoint
Range
1
Sequence=Auto
Auto
1234
1432
2143
2341
3214
3412
4123
4321
2
StageUp= xxx sec
3
StageDn= xxx sec
4
MinST-ST=xx min
15
5 - 40
MinSP-ST xx min
3 - 30
Comp #1
Disable / Enable
Comp #2
Disable / Enable
Comp #3
Disable / Enable
5
Comp #4
5
Disable / Enable
Table 43, MENU 17 Head Pres Spt
Values for R-22 refrigerant, ( ) indicates Centigrade values
Screen
Display
Factory Setpoint
Range
1
MinLift 50%=xxx
90 (621)
70 - 100 (483 - 690)
2
MinLift100%=xxx
120 (828)
100 - 140 (690 - 966)
3
DeadBand 50%= x.x
50
0 - 255
4
DeadBand100% = x.x
90
0 - 255
5
Cond Pres 1 = xxx
200
180 - 220
6
Cond Pres 2 = xxx
300
280 - 320
7
StageUpErr= xxx
400 (2760)
300 - 990 (2070 - 6830)
8
StageDnErr = xxx
100 (690)
50 - 400 (340 - 2760)
Table 44, MENU 17 Head Pres Spt
Values for 134a refrigerant, ( ) indicates Centigrade values
Screen
Display
Factory Setpoint
Range
1
MinLift 50%=xxx
50 (345)
50 - 80 (345 - 552)
2
MinLift100%=xxx
70 (483)
80 - 122 (552 - 841)
3
DeadBand 50%= x.x
23
0 - 255
4
DeadBand 100% = x.x
50
0 - 255
5
CND PRS 1 = xxx
128
180 - 220
6
CND PRS 2 = xxx
201
280 - 320
7
StageUpErr= xxx
275 (1897)
300 - 990 (2070 - 6830)
8
StageDnErr = xxx
57 (393)
50 - 400 (340 - 2760)
Table 45, MENU 18 Demand Limits
Screen
Display
Factory Setpoint
Range
1
Demand Lim= xstg
3
Not Changeable at this screen
2
DemandSg= xx.x ma
Actual Value
Indicates the Magnitude of the
Demand Limit Signal
Table 46, MENU 19 Time / Date
Screen
Display
Factory Setpoint
Range
1
Time= xx:xx:xx
Actual Time
2
Mon xx/xx/xx
Actual Day and Date
Содержание ACZ 045A
Страница 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Страница 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Страница 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Страница 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Страница 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Страница 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Страница 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Страница 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Страница 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Страница 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Страница 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...