66
IOMM ACZ/AGZ-1
Controller Inputs /Outputs
Analog Inputs
Analog inputs are used to read the various temperatures and pressures on the chiller as well as any
customer supplied 4-20mA reset signals. The controller’s internal regulated 5Vdc and 12Vdc supplies
provide correct operating voltage for the sensors. See Table 22 for details.
Table 22, Analog Inputs
Input
LED
Description
Location
Range
Resolution
0
0
Leaving Chilled Water Temp
Leaving Chw nozzle
-40 to 263°F
0.1°F
1
1
Circuit #1 Evap Pressure
Circuit #1 Suction Line
0 to 145 psi
0.1 psi
2
2
Circuit #2 Evap Pressure
Circuit #2 Suction Line
0 to 145 psi
0.1 psi
3
3
Circuit #1 Cond Pressure
Compressor Discharge Line-
20 to 450 psi
0.5 psi
4
4
Circuit #2 Cond Pressure
Compressor Discharge Line-
20 to 450 psi
0.5 psi
5
5
Voltage Ratio Signal
EnGinn Power Supply
4.1 to 5.1 VDC
--
6
6
Chw Water Reset
Supplied by others
4 to 20 mA DC
--
7
7
Demand Limit Signal
Supplied by others
4 to 20 mA DC
--
8
8
Entering Evap Water Temp
Entering Chw Nozzle
-40 to 263°F
0.1°F
9
9
Entering Cond Water Temp
Enter Cond Water Nozzle
-40 to 263°F
0.1°F
10
10
Leaving Cond Water Temp
Leaving Cond Water Nozzle
-40 to 263°F
0.1°F
11
11
% Total Unit Amps
Control Cabinet
0 to 4 VDC
--
12
12
Circuit #1 Suction Temp
Circuit #1 Suction Line
-40 to 263°F
0.1°F
13
13
Circuit #2 Suction Temp
Circuit #2 Suction Line
-40 to 263°F
0.1°F
14
14
Circuit #1 Liquid Line Temp
Circuit #1 Liquid Line
-40 to 263°F
0.1°F
15
15
Circuit #2 Liquid Line Temp
Circuit #2 Liquid Line
-40 to 263°F
0.1°F
Digital Inputs
All Digital Inputs are 24Vac. At 7.5Vac to 24Vac the digital input contacts are considered closed.
Below 7.5Vac, the contracts are considered open. See Table 23 for details and operating
characteristics.
Table 23, Digital Inputs
Input
LED
Description
Circuit
Closed
Open
0
0
Mechanical High Pressure Switch
Circuit #1
Normal
Alarm
1
1
2
2
Motor Protect Switch Compressor
Compressor #1
Normal
Alarm
3
3
4
4
Motor Protect Switch Compressor
Compressor #3
Normal
Alarm
5
5
System Switch
Unit
Run
Stop
6
6
Phase/Voltage Monitor
Unit
Normal
Alarm
7
7
Pumpdown Switch
Unit
Pmp Dn
Normal
8
8
Mechanical High Pressure Switch
Circuit #2
Normal
Alarm
9
9
10
10
Motor Protection Switch
Compressor #2
Normal
Alarm
11
11
12
12
Motor Protection Switch
Compressor #4
Normal
Alarm
13
13
Chiller Remote Stop Switch
Unit
Run
Stop
14
14
Evap Water Flow Switch
Unit
Run
Stop
15
15
Pumpdown Switch
Circuit #2
Pmp Dn
Normal
Relay Board Outputs
All of the MicroTech panel outputs are controlled by solid-state relays which are driven by the model
250 controller. The controller activates a solid-state relay by sending a “trigger” signal to the output
board via the attached ribbon cable. The relay responds to the trigger by lowering it’s resistance
which allows current to flow through it’s “contacts”. When the controller removes the trigger signal,
the relay’s resistance becomes very high, causing the current flow to stop. The outputs are
individually protected by a 5 amp fuse mounted on the output board adjacent to each relay. Table 24
provides additional information about each output. Refer to the MicroTech Staging schematic for
digital output wiring.
Содержание ACZ 045A
Страница 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Страница 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Страница 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Страница 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Страница 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Страница 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Страница 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Страница 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Страница 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Страница 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Страница 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...