100
IOMM ACZ/AGZ-1
Service
CAUTION
1. Service on this equipment is to be performed by qualified refrigeration personnel familiar
with equipment operation, maintenance, correct servicing procedures, and the safety
hazards inherent in this work. Causes for repeated tripping of safety controls must be
investigated and corrected.
2. Disconnect all power before doing any service inside the unit.
3. Anyone servicing this equipment shall comply with the requirements set forth by the EPA
in regards to refrigerant reclamation and venting.
Filter-Driers
A replacement of the filter-drier is recommended any time excessive pressure drop is read across the
filter-drier and/or when bubbles occur in the sightglass with normal subcooling. The maximum
recommended pressure drops across the filter-drier are as follows:
Table 58, Filter-Drier Pressure Drop
PERCENT CIRCUIT
LOADING (%)
MAXIMUM RECOMMENDED PRESSURE
DROP ACROSS FILTER DRIER PSIG (KPA)
100%
10 (69)
75%
8 (55.2)
50%
5 (34.5)
25%
4 (27.6)
The filter-drier should also be changed if the moisture indicating liquid line sightglass indicates excess
moisture in the system.
During the first few months of operation the filter-drier replacement may be necessary if the pressure
drop across the filter-drier exceeds the values listed in the paragraph above. Any residual particles
from the condenser tubing, compressor and miscellaneous components are swept by the refrigerant
into the liquid line and are caught by the filter-drier.
Liquid Line Solenoid Valve
The liquid line solenoid valves that shut off refrigerant flow in the event of a power failure does not
normally require any maintenance. The solenoids may, however, require replacement of the solenoid
coil or of the entire valve assembly.
The solenoid coil can be checked to see that the stem is magnetized when energized by touching a
screwdriver to the top of the stem. If there is no magnetization either the coil is bad or there is no
power to the coil.
The solenoid coil may be removed from the valve body without opening the refrigerant piping after
pumpdown. For personal safety shut off and lock out the unit power.
The coil can then be removed from the valve body by simply removing a nut or snap-ring located at
the top of the coil. The coil can then be slipped off its mounting stud for replacement.
To replace the entire solenoid valve follow the steps involved when changing a filter-drier.
Содержание ACZ 045A
Страница 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Страница 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Страница 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Страница 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Страница 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Страница 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Страница 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Страница 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Страница 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Страница 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Страница 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...