IOMM ACZ/AGZ-1
59
Cir #2 Starts - Counts the number of starts for circuit #2. Note: If power is lost to the controller,
this data is lost and will start counting over. When power is applied and kept on, the controller
will allow 10 starts for circuit #1 as the lead circuit, then will switch to circuit #2 for the next 10
starts, etc (Automatic Lead/Lag).
Occupied
- |= On, 0 = Off
Flow Failure
- |= Alarm, 0 = Normal
OA Lockout
- Indicates whether your in OA lockout (see OA Lockout SP). No alarm.
Cir#2Lead=On
- Indicates which circuit is in the lead e.g., ½= On, 0 = Off indicates that circuit #2 is in
the lead.
Pmp/Stp #1=0
- |= Auto, circuit #1 allowed to run if cooling capacity is needed, 0 = Pump down circuit
#1 and stop.
Pmp/Stp #2=0
- |= Auto, circuit #2 allowed to run if cooling capacity is needed, 0 = Pump down circuit
#2 and stop.
Solenoid #1
- On a call for cooling on circuit 1, the solenoid is energized and opened.
Solenoid #2
- On a call for cooling on circuit 2, the solenoid is energized and opened.
Frzstat#1Alm
- If circuit #1 fails on freeze, the alarm light on the ZT will light. To clear the alarm, the
Freez-Stat Reset button (located on the Control Panel) must be pushed once to clear.
Frzstat#2Alm
- If circuit #2 fails on freeze, the alarm light on the ZT will light. To clear the alarm, the
Freez-Stat Reset button (located on the Control Panel) must be pushed once to clear.
MinLowPres#1
- If circuit #1 falls below the Minimum Low Pressure Setpoint (default is 10 psig) -
Differential (default is 5 psig) the ZT alarm will light. Once it increases above the Minimum Low
Pressure Setpoint, the alarm will clear.
MinLowPres#2
- If circuit #2 falls below the Minimum Low Pressure Setpoint (default is 10 psig) -
Differential (default is 5 psig) the ZT alarm will light. Once it increases above the Minimum Low
Pressure Setpoint, the alarm will clear.
Compressor #
1 - Compressor 1 is On or Off
Compressor #2
- Compressor 2 is On or Off
Stage 3 to 6
- Indicates how many additional compressor (or unloading) stages are on at the time.
Содержание ACZ 045A
Страница 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Страница 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Страница 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Страница 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Страница 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Страница 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Страница 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Страница 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Страница 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Страница 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Страница 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...