64
IOMM ACZ/AGZ-1
Field Wiring
Interconnecting wiring for the control panel may consist of the following:
•
115Vac power wiring
•
Chilled water pump relay
•
Analog input signals
•
Digital input signals
•
Digital output signals
•
Network communications
•
Communications to a personal computer
•
Telephone line for remote modem access
Power Wiring
The installing contractor provides the unit voltage power source, disconnect, fuses and necessary
wiring for these circuits. All wiring must conform to the National Electrical Code and applicable local
building codes. If the control power source (120Vac) or the evaporator heater power source (120Vac)
or both are supplied from a separate external supply, remove wires 540 and 545 as indicated on the
field wiring diagram.
Power Supplies
There are several internal power supplies used by the controller and related circuitry. The regulated
5Vdc power is supplied by the controller and provides power to all analog inputs into the ADI board.
Do not use this power supply to operate external devices. A 24Vac power supply is available for the
alarm bell option. Wire according to the field wiring diagram.
Analog Input Signals
All sensors and transducers required for normal chiller operation are installed and wired at the factory,
All optional analog signal wiring provided by the installing contractor must be twisted, shielded pair
(Belden #8760 or equal). The optional demand limit and leaving water reset signals are 4 to 20 milliamp
DC signals. The resistive load that conditions the milliamp signal is a 249 ohm resistor mounted on
the ADI board at the factory.
Digital Input Signals
Remote contacts for all digital inputs into the MicroTech controller must be dry contacts suitable for
the 24Vac control signals from the control panel. Do not connect 120Vac power to the digital inputs.
Remote Stop/Start
If remote stop/start control is selected, remove the jumper between terminals #140 and #141 on TB-7.
When the remote stop/start switch is open, the controller will be in the “Off: Remote Sw” mode. The
unit will be enabled when the switch is closed.
Chilled Water Flow Switch
The chilled water flow switch is connected to field wiring terminals #142 and #143 on TB-7. When the
chilled water pump is enabled, the MicroTech controller checks for proof-of-flow through the flow
switch digital input.
Содержание ACZ 045A
Страница 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Страница 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Страница 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Страница 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Страница 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Страница 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Страница 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Страница 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Страница 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Страница 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Страница 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...