Digital Outputs
The digital output board has normally open solid-state relays with an on-board replaceable 5 amp
fuse. The status of all outputs are shown by the individual output red LEDs.
Chilled Water Pump Relay
The optional chilled water pump relay is connected to terminal #10 and #9 on TB-2. When the unit is
enabled, the chilled water pump relay is energized. Be sure the relay coil is rated for a maximum load of
1.8 amps at 120Vac. There is a 5 amp fuse on the digital output board for this control circuit.
External Alarm Annunciator Circuitry
An audible alarm can be connected to the Alarm Output terminals #19 and #28 of TB-3 of the control
panel and is highly recommended to make certain the operator is alerted to any alarm condition. This
output can also be used to alert a building automation system or other controls as required. This
circuit is a 24Vac 1.8 amp maximum load output but can be used as a dry contact or another voltage by
rewiring the circuit. Refer to the unit schematic.
The alarm output can be programmed to activate when an alarm or pre-alarm condition is detected.
The alarm signal is de-energized during normal operations. During a fault alarm condition the alarm
circuit will energize and the alarm status light will be on. During a pre-alarm condition the alarm output
and status light will pulse “on” for one-half second and “off” for four seconds.
Note:
The alarm signal is not active during a power failure and will
not
provide a “Loss of
Power” alarm.
PC Connection
The MicroTech controller can be connected to an IBM or IBM compatible computer for local or remote
system monitoring. Communication network wiring uses low voltage shielded twisted pair cable
(Belden 8760 or equal). The network uses the RS232 communications standard with a maximum cable
length of 50 Feet. An RS232/485 adapter may be used to allow for cable runs to 5000 feet.
Telephone line
If remote access and monitoring of the unit is chosen, then a voice quality direct dial telephone line is
required. The line must be a dedicated line and used only for modem access. The phone line must be
terminated with a standard RJ-11 modular phone plug.
Software Identification
Control software is factory installed and tested in each panel before shipment. The software is
identified by a program code printed on a small label attached to the controller. The software version
may also be displayed on the keypad display by viewing the menu items in the Misc. Setup menu.
Example of typical software identification: AGZ 2 E 01 A
Unit Model
2=R-22, 3=R-134a
Inch-Pound=E, SI=S
Version
Revision
Содержание ACZ 045A
Страница 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Страница 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Страница 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Страница 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Страница 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Страница 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Страница 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Страница 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Страница 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Страница 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Страница 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...