IOMM ACZ/AGZ-1
17
Where rises in liquid lines result in a 0.5 psi loss per foot of lift, a drop in the liquid line results in a rise
in the refrigerant pressure. A substantial drop in the liquid line can assure the existence of pure liquid
at the valve. If it is a substantial increase because of a large drop, the expansion valve selection must
be re-checked to confirm that the valve to be used is not radically oversized.
Liquid Lines from Condensers to Receivers
Receivers in a refrigerant system have both liquid and gas contained within the same vessel. In air-
cooled condenser applications, the condensing temperature can change rapidly resulting in the
requirement for more liquid at a lower temperature and pressure to be introduced into the receiver.
In order for this flow of lower temperature and pressure refrigerant to enter the receiver:
1)
The receiver must be located below the condenser outlet with no restrictions in the line.
2)
The liquid line connecting the condenser and the receiver must be sized for a maximum velocity of
100 fpm. Piping sizes for this are shown in the ASHRAE tables.
Note: If the interconnecting piping described above contains a Seasontrol type head pressure
control valve representing a restriction in the liquid line, a separate vent from the top of the
receiver to the discharge line entering the condenser is required.
Liquid Line Components
To assist in laying out and specifying split systems, the following recommended (or equal)
components can be used.
Table 7, Liquid Line Components
Sporlan Part Number Shown - (Equivalents Are Acceptable)
Unit
Model
Circuit
Nom.R-22
Tons
(mbh)
Filter
Drier
Solenoid
Valve
Sight
Glass
Expansion
Valve
Unit Conn.
In/Out
ACZ030A
Circuit #1
15.9 (191)
C-487
E19S270
SA-17S
OVE-20
7/8-1-3/8
ACZ035A
Circuit #1
15.9 (191)
C-487
E19S270
SA-17S
OVE-20
7/8-1-3/8
Circuit #2
19.1 (229)
C-487
E19S270
SA-17S
OVE-20
7/8-1-3/8
ACZ040A
Circuit #1
19.2 (230)
C-487
E19S270
SA-17S
OVE-20
7/8-1-3/8
ACZ045A
Circuit #1
21.8 (262)
C-487
E19S270
SA-17S
OVE-20
7/8-1-3/8
ACZ050A
Circuit #1
22.1 (265)
C-487
E19S270
SA-17S
OVE-20
7/8-1-3/8
Circuit #2
26.8 (322)
C-967
E19S270
SA-17S
OVE-30
7/8-1-3/8
ACZ055A
Circuit #1
26.8 (322)
C-967
E19S270
SA-17S
OVE-30
7/8-1-3/8
Содержание ACZ 045A
Страница 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Страница 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Страница 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Страница 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Страница 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Страница 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Страница 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Страница 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Страница 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Страница 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Страница 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...