IOMM ACZ/AGZ-1
49
Digital Inputs
Note:
All Digital Inputs are 24Vac supplied by transformer T2 in the control panel. Do not use
inputs from another power supply external to the unit. This can cause failure of the Global
UNT controller.
Table 18, Digital Inputs
Input
Description
Location
Closed
Open
BI-1
Time Clock
Field Installed to TB-7 #140 &
#141
Run
Stop
BI-2
Auto / Pumpdown and Stop Switch
Circuit #1
Control Panel
Run
Pumpdown
Stop
BI-3
Auto / Pumpdown and Stop Switch
Circuit #2
Control Panel
Run
Pumpdown
Stop
BI-4
Chilled Water Flow Switch
Field Installed to TB-7 #142 &
#143
Run
Stop
Relay Outputs
All of the relay outputs are controlled by the Global UNT controller. The relays are double pole
double throw relays with contacts rated for 120Vac - 7.0 amp and a 24Vac holding coil. Refer to the
unit staging schematic.
Table 19, Relay Board Outputs
Relay Output
Number
Output
Description
1
Circuit #1 Liquid Line Solenoid Valve
2
Circuit #2 Liquid Line Solenoid Valve
3
Compressor #3 Contactor M3
4
Compressor #4 Contactor M4
5
Spare
6
Spare
7
Low Pressure Relay Circuit #1
8
Low Pressure Relay Circuit #2
Reset Options
The Global UNT controller is capable of one reset option. The reset option should be selected at the
time of purchase. Outside Air is the standard option and a Zone Terminal is necessary to activate this
option or any other reset option. Other reset options, such as chilled water, are available and requires
a software download. Field modifications can be accomplished with the Global UNT Interface Kit Part
Number 0074642001; consisting of cable supply, cable pro, and connector board.
Outside Air Reset
When selected, a Outdoor Air Temperature (OAT) sensor is connected to TB-7 terminals #134 and
#135. Four variables are used to setup the reset ramp that calculates the Actual Leaving Water
Setpoint. These are: Leaving Water Setpoint (AI-4), Reset Band selected with a Zone Terminal,
Outdoor Air High Limit (OAHL), and Outdoor Air Reset Band (OARB).
Figure 23, Outside Air Reset
LWR B
LWSP
OALL
OA HL
OA R B
(OALL=OAHL - OARB)
Содержание ACZ 045A
Страница 6: ...6 IOMM ACZ AGZ 1 Figure 3 Clearance Requirements...
Страница 27: ...IOMM ACZ AGZ 1 27 Figure 12 AGZ AM Single point Connection with FanTrol...
Страница 28: ...28 IOMM ACZ AGZ 1 Figure 13 AGZ AM Single point Connection with SpeedTrol...
Страница 29: ...IOMM ACZ AGZ 1 29 Figure 14 AGZ AM Unit Control Schematic UNT...
Страница 30: ...30 IOMM ACZ AGZ 1 Figure 15 AGZ AM Staging Schematic UNT...
Страница 31: ...IOMM ACZ AGZ 1 31 Figure 16 AGZ AM MicroTech Controller Schematic...
Страница 32: ...32 IOMM ACZ AGZ 1 Figure 17 AGZ AM Unit Control Schematic MicroTech...
Страница 33: ...IOMM ACZ AGZ 1 33 Figure 18 AGZ AM Staging Schematic MicroTech...
Страница 34: ...34 IOMM ACZ AGZ 1 Figure 19 ACZ Field Connection Diagram No Capacity Control...
Страница 35: ...IOMM ACZ AGZ 1 35 Figure 20 ACZ Field Wiring Diagram Capacity Control Staging...
Страница 104: ...Post Office Box 2510 Staunton Virginia 24402 2510 USA 800 432 1342 www mcquay com...