6 Useful Features
40
R4G/R4GE series
LOCK
OCP
SET
OVP/
CV
CC
V
A
OUTPUT
REMOTE
3. Usage example of the delay trigger setting "Slave Local" at master/slave configuration
In the "Slave Local", only the operation of the [OUTPUT ON/OFF] switch is master/slave, and the
voltage/current preset values and delay trigger setting values can be set to the master and slave units
respectively.
The output timing of each unit can be freely adjusted as desired with a single click of the [OUTPUT
ON/OFF] switch on the master unit.
a. Setting the slave units
Select "Local" for the "Slave Local/Remote" setting in the delay trigger menu.
As an example here, set the delay trigger "dly" to "ON" and both ON and OFF delay times to 2.0
seconds.
In the "Slave Local", the voltage/current preset values and OVP/OCP set values need to be set
for the master and slave units respectively. Set them for each unit.
*
In the "Slave Local", only the operation of the [OUTPUT ON/OFF] switch on the master unit
is applied to the slave units. Note that even if the [OUTPUT ON/OFF] switch is operated on
a slave unit the output cannot be turned on or off.
b. Setting the master unit
As an example here, for the delay trigger of the master unit, set "dly" to "ON" and set the ON and
OFF delay times to 1.0 sec.
c.
Starting and stopping output
Pressing the [OUTPUT ON/OFF] switch of the master unit during the output stop starts the
countdown for both master and slave units, and all units turn on the output when the countdown
reaches "0".
Pressing the [OUPUT ON/OFF] switch of the master unit after the output turns on starts a
countdown for both the master and slave units, and all units turn off the output when the
countdown reaches "0".
OUTPUT
ON
Master
(+ 5.00V)
Slave
(+15.00V)
OUTPUT
OFF
1.0sec
2.0sec
1.0sec
2.0sec
"Local"
Slave unit can be set.
* The delay trigger can be individually set to each unit.
REMOTE LED is blinking.