Flow Indicator Totaliser 1006H
REF NO:m16Aom101
Issue No: 03
3.8 Isolation specification
ISOLATION RESISTANCE
Between power supply terminal and ground terminal: 500
VDC, 50MΩ
MEASURED INPUT
TERMINAL
Isolated from other input/output terminals. Not isolated from
24Vdc supply (Transmitter power supply) and internal circuit.
24V DC SUPPLY FOR
TRANSMITTER
Not isolated from the measured input terminal & internal
circuit, isolated from other input/output terminals.
RETRANSMISSION
OUTPUT TERMINAL
Isolated from other input/output terminals and internal circuit.
CONTACT INPUT
TERMINAL
Isolated from other input/output terminals and internal circuit.
RELAY CONTACT O/P
TERMINAL (DIGITAL INPUT)
Isolated from other input /output terminals and internal
circuit.
RS
-
485 COMMUNICATION
TERMINAL
Isolated from other input/output terminals and internal circuit.
POWER SUPPLY
TERMINAL
Isolated from other input / output terminals and internal
circuit.
GROUND TERMINAL
Isolated from other input/ output terminals and internal
circuit.
3.9 Environmental Specification
OPERATING TEMPERATURE
0 to 55
C
STORAGE TEMPERATURE
0 to 70
C
HUMIDITY
30 to 90% RH (non-condensing)
WARM UP TIME
>10 Minute
EFFECT OF AMBIENT
TEMPERATURE
For Voltage Input:
0.005% of FS/
C or less
For analog output:
0.010% of FS/
C or less
3.10 Alarm Specification
ALARM TYPES
Flow high limit, Flow low limit
BATCHING ALARM
Pre warn and set point
SETTING RANGES FOR
PROCESS VALUE
ALARMS
Flow (PV) Alarms:
Min = Zero of individual I/P type
Max = Span of individual I/P type
3.11 Display Specification
PV DISPLAY/
INTEGRATED TOTAL
6 digit red 7 segment display for flow rate/Integrated total
PARAMETER DISPLAY
Same 6 digit red 7 segment display flow rate/Integrated total
STATUS DISPLAY
Red LEDs (for alarm & Batch)