1
User Manual
23
Flow Indicator Totaliser 1006H
REF NO:m16Aom101
Issue No: 03
*
Note: - Retransmission Output is Corresponds to the ZR1 (Zero Value) and FS1 (Full
Scale Value).
Batch Mode:
If „
Batch
Mode’
(bat md
) is selected to „Counter‟, then two parameters “
Batch count
”(bt Cnt)
and “
No of Batches”
(no bt) will be displayed in Configuration mode.
If „Batch
Mode’
is selected to „Normal‟, then two parameters will not be displayed.
Input Type:
Based on requirement, user can select input type. It will be either Voltage or Current or Pulse.
Instrument Type:
If “
instrument type
” is set as indicator, then
Prewarn
and
Setpoint
parameter will not be
displayed in Program mode.
Square root:
If user selects this mode as „yes‟, flow rate will calculated using square root algorithm.
Alternatively linear calculation will be done.
Digital Input:
If
Digital input
is
selected as „yes‟ than only digital input will work. One digital input is there For
Start/Stop Function.
DIG.I/P+: +24VDC
DIG.I/P- : GND
When any of these inputs is connected to DIN-, it will perform its specific function.
Digital Filter:
If
Digital filter
is selected as „yes‟ than in programming mode user can see „
filter
no‟
parameter. If selected
‘
no‟ then
’filter
no‟ will not be displayed
.
Time base:
Time base is used for calculation & display of flow rate.
Time base Setting details
Value of Integrated total for time period of t (in seconds) will be
Integration total= (flow rate *
time„t‟ in seconds)/divisor
Batch counter and no of batches:
These parameters will be displayed only if the
‟Batch mode‟ is selected to counter type.
No of batches
: Set the parameter according to the requirement. It decides how much
batches are to be taken
Batch counter:
It will be incremented by 1 whenever a new batch is started by START
key in run mode. When batch
counter value becomes equals to „no of batches‟ value,
then it will not
start
new batch.
Select
Time base
Divisor
0
Second
1
1
Minute
60 (1 x 60)
2
Hour
3600(60 x 60)
3
Day
86400(24 x 60 x 60)