8.4.2 Configuration mode 

Configuration mode provides facility to configure type of mode, type of input, baud rate for 
communication, etc. Every parameter is explained in the next section. 

8.4.2.1 Configuration Mode Parameters of 1006H 

Sr. 

No. 

Name  

Description 

No Of 

Digit 

Lo Limit 

Hi Limit 

Batch Mode 

Type Of Mode, For Flow Control 

Normal, Counter 

Input Type 

Type Of Input 

0-5V, 1-5V, 0-20mA, 4-20mA, 

Pulse 

Type Of 
Instrument 

Type Of Instrument, Which You Want To 
Use. 

Indicator/ 

Totaliser/Counter 

Square Root 

Mode Of Linearization 

Yes/No 

Digital Input 

To Be Used To start and stop batch 

 

Yes/No 

Digital Filter 

If Yes Than In Programming Mode It Will 
Show Filter No. 

Yes/No 

  

Time Base 

For Calculation/Display Of Flow Rate 

Sec, Min, Hour, Day 

ZR1 

Zero Value

*

 

000000 

999998 

FS1 

Full Scale Value

*

 

000000 

999999 

10 

No Of Batches 

 

00 

99 

11 

Batch Count 

Counter Will Count How Much Batches 
 Has Been Taken 

00 

99 

12 

rounding 

Base Rounding value of last digit  

1,2,5,10 

13 

Cut Off 

 

000.0 

999.9 

14 

DP 

Decimal Point  

0,0.1,0.01,0.001 

15 

SF1 

Full Scale For Segment 1 

000000 

999999 

16 

FL1 

% Age Of Full Scale (Segment 1) 

10,20,30,40,50,60,70,80,90,100 

17 

SF2 

Full Scale For Segment 2 

000000 

999999 

18 

FL2 

% Age Of Full Scale (Segment 2) 

10,20,30,40,50,60,70,80,90,100 

19 

SF3 

Full Scale For Segment 3 

000000 

999999 

20 

FL3 

% Age Of Full Scale (Segment 3) 

10,20,30,40,50,60,70,80,90,100 

21 

SF4 

Full Scale For Segment 4 

000000 

999999 

22 

FL4 

% Age Of Full Scale (Segment 4) 

10,20,30,40,50,60,70,80,90,100 

23 

SF5 

Full Scale For Segment 5 

000000 

999999 

24 

FL5 

% Age Of Full Scale  (Segment 5) 

100 

25 

Baud Rate 

Baud Rate 

9600,19200 

26 

Serial No 

Serial No 

01 TO 99 

27 

Pout 

Pout 

0001 TO 9999 

28 

 Default           
Display 

 Default Display 

Batch Total/Integration Total 

(Bat Tot/Int Tot) 

29 

password 

password 

0000-9999 

30 

Conversion              
Factor 

Conversion Factor 

00.00-99.99 

31 

Clear  
Total  

To Clear Integration /Batch Total And Roll 
Count 

3210 

32 

K-FAC 

K-FACTOR  

 

000000-999999 

33 

Pulse Time 

Averaging of pulse input 

00-20 

34 

Frequency 

For  pulse input higher than 300Hz Select 
High else select Low 

 

Low/High 

35 

Pulse width 

Pulse width of pulse input in millisecond 

00-50 

36 

Multiplying 
Factor 

It is the factor for pulse input in counter 
mode 

000000-999999 

Содержание 1006H

Страница 1: ...DICATOR TOTALISER 1006H Masibus Automation Instrumentation Pvt Ltd B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India 91 79 23287275 79 91 79 23287281 82 Email support masibus com...

Страница 2: ...ification 9 3 12 Communication 10 3 13 Other Specification 10 3 14 Physical Specification 10 4 FRONT AND REAR PANEL DESCRIPTION 11 4 1 Front Panel Description 11 4 2 Rear Panel Diagram 11 5 MECHANICAL...

Страница 3: ...9 1 Input Calibration 29 9 2 Output Calibration 29 9 2 1 out zero and out span 29 10 COMMUNICATION GUIDELINES 30 10 1 Introduction 30 10 2 Function Code for Modbus 30 10 3 Modbus RTU protocol address...

Страница 4: ...nu driven with user understandable prompts For protecting programmed data password protection facility is provided Integrated total batch total and roll count are cleared by special password The produ...

Страница 5: ...nts before using the product If the product is different from that which you have ordered if any parts or accessories are missing or if the product appears to be damaged contact your sales representat...

Страница 6: ...rify the ratings of the output devices and the inputs are as specified o Provide Power from a single phase instrument power supply If there is a lot of noise in the power line insert an insulating tra...

Страница 7: ...lowable signal source Resistance 0 031 100 or less ALLOWABLE INPUT VOLTAGE DC voltage 20V DC NOISE REJECTION RATIO Common Mode 100db Normal mode 40db RESPONSE TIME Input to relay o p 1 second Input to...

Страница 8: ...AGE Flow alarm Batch relay NUMBER OF RELAY CONTACT OUTPUTS 2 Flow alarm relays Batch relays RELAY CONTACT RATING 250VAC 5Amps RELAY CONTACT TERMINAL 2 Common NO 3 6 Display Unit Specification PROCESS...

Страница 9: ...ATION TERMINAL Isolated from other input output terminals and internal circuit POWER SUPPLY TERMINAL Isolated from other input output terminals and internal circuit GROUND TERMINAL Isolated from other...

Страница 10: ...600 19200 bps MAX CONNECTABLE CONTROLLERS INDICATOR 32 ADDRESS RANGE 1 to 99 3 13 Other Specification SQUARE ROOT EXTRACTION Applicable DIGITAL FILTER Applicable TIME BASE UNIT Second minute hour day...

Страница 11: ...1 User Manual 11 Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 4 FRONT AND REAR PANEL DESCRIPTION 4 1 Front Panel Description 4 2 Rear Panel Diagram...

Страница 12: ...ument with the panel using two side brackets All the electrical connections to be done at back panel on screw type terminals Make sure that no wire is connected loosely to avoid generation of spark an...

Страница 13: ...1 User Manual 13 Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 6 TERMINAL CONNECTION DETAILS...

Страница 14: ...Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 User Manual 14 7 WIRING DIAGRAM 7 1 Wiring Diagram of 1006H...

Страница 15: ...dicator Totaliser 1006H REF NO m16Aom101 Issue No 03 7 2 Wiring Diagram and Jumper Setting of Pulse Input 7 2 1 NPN Proximity Input Jumper Setting 7 2 1 A NPN Proximity Input 7 2 1 B Dry Contact With...

Страница 16: ...Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 User Manual 16 7 2 2 PNP Proximity Input Jumper Setting 7 2 2 A PNP Proximity Input 7 2 2 B Dry Contact With PNP Input Jumper Setting...

Страница 17: ...1 User Manual 17 Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 7 2 2 C Wet Contact 10Vdc With PNP Input Jumper Setting 7 2 2 D Wet Contact 10Vdc With PNP Input Jumper Setting...

Страница 18: ...OR SHIFT 1 It will enter into the submenu when main menu is enabled and shows submenu s value 2 It will select the digit to modify when value is edited 3 It will start batch if pressed when IT BT are...

Страница 19: ...tal is updated continuously proportional to input Rollover Count RC This is a two digit value displayed as the rollover that takes place when integrated total gets higher than higher limit When the in...

Страница 20: ...roL Cnt then PASS User Can select the Parameter any of the above prompt to display corresponding value by pressing INDEX key and then pressing START KEY It is digit select key for editing the paramete...

Страница 21: ...or message will be displayed If Low Alarm Zero value error message appears High Alarm value should be greater than Full scale value If user tries to set value of High alarm greater than Full scale val...

Страница 22: ...ff 4 000 0 999 9 14 DP Decimal Point 0 0 1 0 01 0 001 15 SF1 Full Scale For Segment 1 6 000000 999999 16 FL1 Age Of Full Scale Segment 1 10 20 30 40 50 60 70 80 90 100 17 SF2 Full Scale For Segment 2...

Страница 23: ...l work One digital input is there For Start Stop Function DIG I P 24VDC DIG I P GND When any of these inputs is connected to DIN it will perform its specific function Digital Filter If Digital filter...

Страница 24: ...ive different segments of the full scale input in percentage with Full scale engineering value for each segment We have to program the value of flow rate at different inputs Here we are defining five...

Страница 25: ...ters minute conversion factor is 1 then it will simply integrate process value as it is If we change conversion factor 2 then it will divide process value by that factor i e 100 2 50 it integrates tha...

Страница 26: ...ormula for linear mode For any type of input Indication Engineering Value X Zero CALS CALZ X Input signal CALZ Full scale Zero CALZ Value of input applied during zero calibration CALS Value of input a...

Страница 27: ...1 User Manual 27 Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 8 5 Parameter Flow How to operate menu is shown below in the form of flow diagram...

Страница 28: ...Flow Indicator Totaliser 1006H REF NO m16Aom101 Issue No 03 User Manual 28...

Страница 29: ...ill be stored as Span Now the instrument is calibrated 12 Press ESC key to come out from SPAn1 9 2 Output Calibration For output calibration measuring instrument should be at least 3 times accurate 9...

Страница 30: ...ding registers Use to read PV Control RSP output etc 05 Write input registers Use to write digital parameter value 06 Preset Single register Use to write programmable register The error checking field...

Страница 31: ...0mA 3 for 4 20mA 4 for pulse 13 40013 Type of Inst 2 1 R W 0 for indicator 1 for Totaliser 2 for counter 14 40014 Sqrt mode 2 1 R W 0 for Yes 1 for No 15 40015 Digital input 2 1 R W 0 for Yes 1 for No...

Страница 32: ...000 4094 47 40047 Out span 2 1 R W 0000 4095 48 40048 Default out 2 1 R W 0 for yes 1 for no 49 40049 Int total 2 1 Read only 50 40050 Int total 2 2 1 Read only 51 40051 Batch total 2 1 Read only 52 4...

Страница 33: ...DISPLAY RX O P mA LINEAR SQUARE ROOT LINEAR SQUARE ROOT I P 1 60 OPEN OPEN 4 00 4 00 1 60 I P 3 20 UNDER UNDER 4 00 4 00 3 20 I P 4 00 Flow Rate Flow Rate 4 00 4 00 20 00 I P 20 80 Flow Rate Flow Rat...

Страница 34: ...er s power follow the measures in the procedure below If a problem appears complicated contact our sales representative Masibus Automation Instrumentation Pvt Ltd Customer Support Division B 30 GIDC E...

Отзывы: