3.12 Communication
PROTOCOL
Modbus RTU serial
STANDARD
EIA RS-485
MAX. COMMUNICATION DISTANCE
1200 mtrs. (For 9600 bps RS 485)
COMMUNICATION METHOD
2 wire half duplex (RS 485)
DATA FRAME
N, 8, 1
COMMUNICATION RATE
9600, 19200 bps
MAX. CONNECTABLE
CONTROLLERS/ INDICATOR
32
ADDRESS RANGE
1 to 99
3.13 Other Specification
SQUARE ROOT EXTRACTION
Applicable
DIGITAL FILTER
Applicable
TIME BASE UNIT
Second, minute, hour, day
CONVERSION FACTOR
0.00 to 99.99
FIVE POINT LINEARIZATION
Applicable
LOW FLOW CUT OFF
Applicable
3.14 Physical Specification
MOUNTING TYPE
Panel
BEZEL SIZE (in mm)
48 (H) x 96(W) x 110 (D)
CUT OUT DIMENSION (in mm)
44 (H) x 92(W)
WEIGHT
300 gms
IP CLASS
IP20
ENCLOSURE TYPE
Polycarbonate Plastic