Flow Indicator Totaliser 1006H
REF NO: m16Aom101
Issue No: 03
User Manual
32
* For FL1 to FL4
:
To write these parameters:
0 for 10, 5 for 60,
1 for 20, 6 for 70,
2 for 30, 7 for 80,
3 for 40, 8 for 90,
4 for 50, 9 for 100
Sr. No.
Reg. No.
Parameter
Length in
byte
(Word)
Read/Write
36
40036
SF4
2(1)
R/W
37
40037
SF4+2
2(1)
R/W
38
40038
FL4
2(1)
R/W (0-9)*
39
40039
SF5
2(1)
R/W
40
40040
SF5+2
2(1)
R/W
41
40041
FL5
2(1)
R (9)
42
40042
Baud rate
2(1)
R/W (0 for 9600, 1 for 19200)
43
40043
Serial no
2(1)
R/W (01 - 99)
44
40044
Pout
2(1)
R/W (0000-9999)
45
40045
Default display
2(1)
R/W (0 for batch total,
1 for integration total)
46
40046
Out zero
2(1)
R/W (0000-4094)
47
40047
Out span
2(1)
R/W (0000-4095)
48
40048
Default out
2(1)
R/W (0 for yes, 1 for no)
49
40049
Int total
2(1)
Read only
50
40050
Int total+2
2(1)
Read only
51
40051
Batch total
2(1)
Read only
52
40052
Batch total+2
2(1)
Read only
53
40052
Roll count
2(1)
Read only
54
40054
Flow rate
2(1)
Read only
55
40055
Flow rate+2
2(1)
Read only
56
40056
K factor
2(1)
R/W
57
40057
K 2
2(1)
R/W
58
40058
Pulse time
2(1)
R/W (0-20)
59
40059
Frequency
2(1)
R/W (0 for LOW, 1 for HIGH)
60
40060
Pulse width
2(1)
R/W (0-50)
61
40061
Mul 2
2(1)
R/W
62
40062
Mul factor
2(1)
R/W
63
40063
Flow Rate dp
2(1)
Read only
Coil Registers
64
1
Pre-warn relay/
Low alarm relay
1
R, digital (1 for ON, 0 for OFF)
65
2
Set point relay/
High alarm relay
1
R, digital (1 for ON, 0 for OFF)
66
5
Stop batch
0000
W, digital
67
5
Start batch
FF00
W, digital