Flow Indicator Totaliser 1006H
REF NO: m16Aom101
Issue No: 03
User Manual
24
Note:
To reset batch counter, Enter in batch count (bt Cnt ) parameter in configuration
mode. Press “Start” key to see its value. Now if user presses “Stop” key Batch counter
value will be cleared to 0.
Cut off: (Low flow cut-off)
Cut off could be set to 0000 to 0100.
Cut off will display the % value.
Cutoff value = Cutoff parameter (in %)*Full scale value
If full scale value is 10000 and cut off is 5%
Then cut off value will be calculated as
= (5/100)*10000 = 500.
So, if the displayed flow rate (displayed at upper window) is less than 500, it will not be
added in integration.
Decimal Point Selection:
Decimal point selection will be given from the configuration mode.
Five point Linearization:
This instrument has feature of five-point linearization. User can define up-to five different
segments of the full-scale input (in percentage) with Full-scale engineering value for each
segment. We have to program the value of flow rate at different inputs.
Here we are defining five scale factors for the current input 4 mA to 20m
A. Let‟s have one
example to understand this concept.
For Example:
ZR = 00000 and FS = 10000, Let us assume the Unit is current input mode.
In above example
Flow rate on Display varies between:
0
– 2000 for input of 0 % – 10%
2000
– 4000 for input of 10% – 50%
4000
– 4500 for input of 50 % – 60%
4500
– 7500for input of 60 % – 80%
7500
– 10000 for input of 80 % – 100%
If user wants a flow to be linear throughout the span than configure this parameter as:
SF1 = FS1, FL1 = 100 %.
User is not required to initialize SF2, SF3, SF4, SF5, FL2, FL3, FL4 and FL5.
Select
Decimal position
0
No decimal
0.1
One decimal
0.01
Two decimals
0.001
Three decimals
N
o.
Flow
rate
Value
Param
eter
Display
Value
Input
Current
mA
1
FL1
10%
SF1
2000
5.6
2
FL2
50%
SF2
4000
12.0
3
FL3
60%
SF3
4500
13.6
4
FL4
80%
SF4
7500
16.8
5
FL5
100%
SF5
10000
20