UK | 6 Settings main menu
78
6.11 Supplementary heating
(ZP 1, switching contact HP)
Additional circuit board “ZP 1” = accessory for
ventilation units:
310/410
320/470
170
160 Flat
300 Flat
. Option for connecting to
main circuit board with switching contact „HP“
on
310/410
320/470
160 Flat
300 Flat
Trio
.
Parameter
Setting
Supplementary
heating
no /
yes
Hysteresis
setpoint temperature
0.1 ...
0.3
... 1 K
i
For additional information about the
supplementary heating
Chapter 9.4.
Supplementary heating, e.g. using an electric
or hydraulic heat register. The
Hysteresis
setpoint temperature
parameter can still be
set for adjustment purposes. The hysteresis
relates to the room setpoint temperature set in
the short code menu
Chapter 5.3.
6.12 Pressure consistency (ZP 2)
Additional circuit board “ZP 2” = accessory for
ventilation units:
310/410
320/470
170
160 Flat
300 Flat
.
Parameter
Setting
Operation with con-
stant pressure
no /
yes
Reference
Pressure
/ volumes
Reference volumetric
flow
0 ...
200
... 500 m³/h
Reference pressure
10 ...
200
Pa
For additional information about control with
constant pressure
Chapter 10 or accesso-
ries instructions.
6.13 Filter monitoring (ZP 2)
through differential pressure
measurement
Additional circuit board “ZP 2” = accessory for
ventilation units:
310/410
320/470
170
160 Flat
300 Flat
.
Parameter
Setting
Filter monitoring
no /
yes
Permissible delta p
10 ...
80
... 200 %
For additional information about filter
monitoring
Chapter 10 and accessories
instructions.
6.14 EnOcean wireless
(plug-in module E-SM)
Parameter
Setting
EnOcean wireless
no /
yes
Teach-in mode
inactive
/ active
Unit list
inactive
/ active
Unlearn units
*
* Here you can either unlearn all or
just individual EnOcean wireless units.
i
For additional information about the
EnOcean wireless plug-in module
E-SM
Chapter 7.7 or accessories
instructions.
6.15 KNX
(plug-in module K-SM)
Parameter
Setting
KNX
no /
yes
For additional information about the KNX
plug-in module K-SM
accessories instruc-
tions.