UK | 6 Settings main menu
66
Date, time
Parameter
Setting
Date
DD.MM.YYYY
Time
hh:mm
Key lock
Parameter
Setting
Key lock
Inactive: Lock off
active: Lock on
Function with activated key lock:
If there is no input on a main control unit for
2 minutes, the input lock activates. To cancel
the lock, press the touchscreen for 3 seconds.
Interlock for control units (simple control
units)
Simple control units can be locked from a
main control unit. All simple control units
are then deactivated.
Parameter
Setting
Interlock for
control units
Inactive: All simple
control units
are enabled
active: All simple con-
trol units
are deactivated
Status display
i
The
Summer bypass open
,
Frost pro-
tection active
or
Supplementary heat-
ing on
status displays appear when the
relevant function is switched on
Chapter 5.1.
Parameter
Setting
Status display
(symbol display)
no: Display off
yes: Display on
Language
Parameter
Setting
Language
D,
GB, F, I
Room sensor configuration
Parameter
Setting
Room sensor
configuration
Control unit (comfort
control unit), external,
internal
, bus
The temperature determined with the selected
room sensor is used as the room temperature
to control the bypass and any supplementary
heating connected.
Factory setting
Parameter
Setting
Factory setting
Reset
customer level
Reset customer &
installer level
Reset customer level: Owner and tenant set-
tings are reset to the factory setting. Installer
settings at installer level are retained.
Reset customer & installer level:
Factory setting is restored (complete reset).
Comfort control unit (touchscreen control
unit)
Parameter
Setting
Comfort control unit
no: Interface for
comfort control unit
deactivated
yes: Interface for
comfort control unit
activated
i
When commissioning with comfort
control unit briefly connected
1. Connect comfort control unit to the con-
trolled domestic ventilation control (circuit
board A2) in accordance with installation
instructions and switch on.
2. Select this parameter and activate the
interface with “yes”.
3. When commissioning is complete,
deacti-
vate the interface with “no”, otherwise
operation is undefined.
4. Lastly, remove the connection to the con-
trolled domestic ventilation control.