6 Settings main menu | UK
69
Volumetric flow measurement (nominal
ventilation)
Parameter
Setting
Volumetric flow
measurement
(nominal ventilation)
activate
deactivate
After activating the volumetric flow measure
-
ment, the fans are run for a maximum of
3 hours in nominal ventilation.
This allows the supply and exhaust air volu-
metric flows in the building to be calibrated
without the air volumes being changed by
sensor values. The function switches off
automatically after 3 hours.
If
deactivate
is selected or the installer level is
exited, this function switches off immediately.
Volumetric flow of ventilation level
Reduced ventilation „RV“ (in m³/h)
Type
min.
ex
works
max.
WR 310 / WS 320 ..
WR 410 / WS 470 ..
WS 170
WS 160 Flat
WS 300 Flat
Trio
80
80
40
40
80
40
120
160
60
60
100
60
320
490
160
160
300
120
Nominal ventilation „NV“ (in m³/h)
Type
min.
ex
works
max.
WR 310 / WS 320 ..
WR 410 / WS 470 ..
WS 170
WS 160 Flat
WS 300 Flat
Trio
80
80
40
40
80
40
180
240
90
90
150
90
320
490
160
160
300
120
Intensive ventilation „IV“ (in m³/h)
Type
min.
ex
works
max.
WR 310 / WS 320 ..
WR 410 / WS 470 ..
WS 170
WS 160 Flat
WS 300 Flat
Trio
80
80
40
40
80
40
240
320
120
120
200
120
320
490
160
160
300
120
The setpoint volumetric flow setting applies to
both fans. With humidity protection ventilation,
the fans run in interval mode
13 min. RV – 17 min. Off – 13 min RV etc.
We recommend setting the volumetric flow for
NV first.
The RV and IV volumetric flows are set auto-
matically by the control on the basis of the
NV reference value 1/3 less than (RV) and 1/3
greater than (IV).
Example
310/410
320/470
NV 150 m³/h
RV 100 m³/h, IL 200 m³/h.
Example
170
Flat
Trio
NV 90 m³/h
RV 60 m³/h, IL 120 m³/h.
The IV and RV volumetric flows can also be
set manually. Condition:
Volumetric flow Intensive ventilation > Nomi
-
nal ventilation > Reduced ventilation.
EA SA (Exhaust air/supply air) adjustment
Parameter
Setting
EA SA adjustment
RV ventilation level
min. -50 m³/h
max. +50 m³/h
EA SA adjustment
NV ventilation level
min. -50 m³/h
max. +50 m³/h
EA SA adjustment
IL ventilation level
min. -50 m³/h
max. +50 m³/h
EA = exhaust air, SA = supply air
Setting ex factory = 0 m³/h
Supply and exhaust air volumes must be
balanced over the entire application area. Nor-
mally the fans automatically ensure a balance
and no adjustment has to be undertaken.