![Maico WS 320 Скачать руководство пользователя страница 64](http://html1.mh-extra.com/html/maico/ws-320/ws-320_commissioning-and-maintenance-instructions_4230730064.webp)
UK | 6 Settings main menu
64
5.2 Main menus
In the
Settings
main menu, you can undertake
the basic system settings and calibrate the ven-
tilation unit. For more information
Chapter 6.
In the
Retrieve
main menu, you can retrieve
the current system values/statuses
Chapter
7.
5.3 Short code/quick choice menus
Operating mode
Ventilation level
Room temperature
Season
Operating mode short code
Set the basic mode of operation of the ventila-
tion unit with the operating mode.
Operating modes
Mode of operation
Auto time
Automatic time
programme
Auto sensor
Automatic operation
with sensor control
Manual
Manual mode
ECO mode, supply air Energy-saving sum-
mer operation with
supply air fan
ECO mode, exhaust
air
Energy-saving sum-
mer operation with
exhaust fan
Off
Standby mode
(fans Off)
Choose between
automatic operating
modes
(Auto time, Auto sensor) and
manual
operating modes
(Manual, ECO mode sup-
ply air, ECO mode exhaust air and Off). For
more information
operating instructions,
Chapter 8.2.
Ventilation level short code
Activates the ventilation level. The setting is
available in a manual operating mode.
Ventilation level
Mode of operation
Ventilation for
humidity protection
Interval operation,
approx. 43 % of reduced
ventilation (according to
DIN 1946-6)
Ventilation level 1 Continuous operation
with reduced ventilation
Ventilation level 2: Nominal ventilation
Pulse ventilation:
Time-limited intensive
ventilation (with timer)
Ventilation level 3 Intensive ventilation
For more information
operating instructions
and Chapter 8, Special functions.
Room temperature short code
Actual room temperature:
The actual room
temperature currently measured appears in
the standard display.
Room setpoint tem-
perature:
If optional supplementary heating is
connected, you can adjust the room setpoint
temperature here. The ventilation unit then
regulates the room temperature to the speci-
fied value.
Season short code
Activates the
Summer
or
Winter
season.
The season has to be changed manually.
When
Summer
is selected:
The summer
time programme starts, if the
Auto Time
operating mode is selected. With
summer
,
the
ECO mode supply air
and
ECO mode
exhaust air
operating modes are available.
The cooling function with bypass and brine
earth heat exchanger is enabled. A connected
supplementary heating register is disabled.
When
Winter
is selected:
The winter time
programme starts, if the
Auto Time
operating
mode is selected. The cooling function with
bypass and brine earth heat exchanger is
disabled. A connected supplementary heating
register is enabled.