Page 37
3.8.10.
54B
Checking for Spillage
1. Close all doors and windows.
2. Turn the fire on at full rate and leave it
burning for 5 minutes.
3. Test for spillage using a smoke match (in
a ‘Blume Tube’) about 12mm under the
centre of the top louvre on the ceramic
fireback.
4. If the smoke spills out into the room,,
repeat the test after a further 10 minutes
5. If the fire shows tendency to spill, this
may indicate either an installation fault or
a flue construction fault.
Disconnect
the fire and seek expert advice
.
The fuel effect must be laid in
accordance with the instructions
prior to commencing the spillage
test.
I there are any extractor fans in
the nearby rooms then repeat
the smoke match test with all
these fans operating and any
interconnecting doors open
between the fans and the fire.
SMOKE
MATCH
Figure 57 – Spillage Test
3.8.11.
55B
Instructing the User
The installer must hand over these
instructions to the user and explain how to
operate this fire, stressing the importance of
having the fire checked and serviced
regularly. An annual service is
recommended.
It is mandatory as part of the
gas installation that the installer
instructs the user on the correct
operation and care of their
appliance.
Содержание ARIA
Страница 8: ...Page 4 This page is left intentionally blank...
Страница 28: ...Page 24 This page is left intentionally blank...
Страница 42: ...Page 38 This page is left intentionally blank...
Страница 53: ...Page 49 This page is left intentionally blank...
Страница 54: ...Page 50 This page is left intentionally blank...
Страница 55: ...Page 51 This page is left intentionally blank...