Page 27
3.5.
14B
Appliance Location
The fire must be fitted on a flat non-combustible base. In addition a non-combustible hearth or
physical barrier with minimum dimensions shown in figures below
should be provided in front
of the fireplace opening where relevant.
However, with hole in the wall fire installations, where it may be desirable not to include a
hearth with the appliance installation, Building Regulation Approved Document J paragraph
3.40 currently states:-
Appliance should be placed on hearths unless:
a.
they are installed so that every part of any flame or incandescent material will be at
least 225mm above the floor; or
b)
the manufacturer’s instructions state that a hearth is not required.
Burley Magiglo would recommend that a hearth or physical barrier be installed with this
appliance. However, should you decide not to follow our recommendation and do not fit a
hearth or subsequently decide to remove the hearth / physical barrier, then consideration as to
the safety of the occupants of the room should be given.
A suitable proprietary fire surround with a
minimum of 150
o
C rating may be fitted in
front of the fireplace opening.
325
C
150
mm
150
mm
A
He
arth
Fire
Surround
50mm min
(or 12mm with
a fixed fender)
Figure 44
Fireplace Opening Sizes (mm)
16” 18”
Dim Min Max Min Max
A
395
470 445 520
B
555
575 555 575
C
min
280
280
Table 2
Hearth Construction: The hearth material must be non-combustible and a
minimum of 12mm thick, when laid on the floor. Either a 50mm upstand above
the finished floor level must be created or a fixed fender must be used.
Содержание ARIA
Страница 8: ...Page 4 This page is left intentionally blank...
Страница 28: ...Page 24 This page is left intentionally blank...
Страница 42: ...Page 38 This page is left intentionally blank...
Страница 53: ...Page 49 This page is left intentionally blank...
Страница 54: ...Page 50 This page is left intentionally blank...
Страница 55: ...Page 51 This page is left intentionally blank...