Versión 05-12
CRONO
KARESS-TOUCH SCREEN
NOTE: The first time batteries are inserted, the configuration menu is directly accessed
. Where configuration is not automatically accessed or where it is to be modified,
enter SETUP mode (with the thermostat on) by pressing the combination of buttons shown in the figure. Then follow the same steps 1 to 4 as in the previous figure.
5.
START-UP
5.1.
Connect the Fan coil unit (FC) using the diagram supplied..
5.2.
Power the control centre to 230 VAC. The centre will implement the opening cycle. All the grilles will open first and, once the mode has been
detected, they are all closed and work started depending on the temperatures selected in the thermostats..
5.3.
Check that all zones work properly in line with the table below:
5.3.1. 2 PIPES OR 2 PIPES NO SENSOR installation:
If the sensor is installed should be disponibility of treated water in the chiller. If the chiller is not
working it will be necessary to simulate heating or cooling with any device,
1
Switch on the MASTER thermostat, switch to cold at 15 ºC
Switch on the MASTER thermostat, switch to heat at 35 ºC
2
Start the zone thermostats and set to 15ºC, check that the
corresponding damper opens on each one.
Start the zone thermostats and set to 35ºC, check that the
corresponding damper opens on each one
3
Wait for the FC to start up and check that cold is produced.
Wait for the FC to start up and check that heat is produced.
4
Select 35ºC on each thermostat, check that the corresponding
grille closes and that the machine stops when the last one is
closed
Select 15ºC on each thermostat, check that the corresponding
grille closes and that the machine stops when the last one is
closed
5.3.2. 2 PIPES+BATTERIE OR 4 PIPES SENSOR installation:
As in the previous example, should be disponibility of treated water in the chiller. In
other case will be necessary to simulate
1
Switch on the MASTER thermostat, switch to cold at 15 ºC
Switch on the MASTER thermostat, switch to heat at 35 ºC
2
Start the zone thermostats and set to 15ºC, check that the
corresponding damper opens on each one.
Start the zone thermostats and set to 35ºC, check that the
corresponding damper opens on each one
3
Wait for the FC to start up and check that cold is produced.
Wait for the FC, the electric coil or the heating valve to start up and
chech that heat is produced.
4
Select 35ºC on each thermostat, check that the corresponding
grille closes and that the machine stops when the last one is
closed
Select 15ºC on each thermostat, check that the corresponding
grille closes and that the machine stops when the last one is
closed . If the electric coil it is activated there is a mandatory delay
of 3 min for the switch off of the fan.
1. Enter SET-UP mode
2. Select Crono mode (+/-)
3. Insert ID number
See ID nubmer in the lable of the control panel
4. Select zone number
ENGLISH
1. Enter SET-UP mode
2. Insert ID number
See ID nubmer in the lable of the control panel
3. Select zone number