R3-TC2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8468 Rev.3 P. 27 / 37
• ALARM SP TYPE
When the SP is changed, actual target temperature gradually changes in a ramp setting until it reaches the final setpoint.
Choose either the setpoint in the ramp transition or the final setpoint should be used for reference of alarm judgment.
ADDRESS
PARAMETER
RANGE
DEFAULT
+325
Loop 1, Alarm 1 SP type
0 : Ramp SP
1 : SP
0
+333
Loop 1, Alarm 2 SP type
+341
Loop 1, Alarm 3 SP type
+581
Loop 2, Alarm 1 SP type
+589
Loop 2, Alarm 2 SP type
+597
Loop 2, Alarm 3 SP type
• ALARM OUTPUT
Specify the output device for alarms.
When one of the control outputs is specified, be sure also to specify ‘Alarm OR’ or ‘Alarm AND’ with its output assignment.
With ‘Alarm OR’ setting, the output is provided if one or more alarms assigned to it are in true conditions. With ‘Alarm AND’
setting it is provided only if all alarms assigned to it are in true conditions.
ADDRESS
PARAMETER
RANGE
DEFAULT
+326
Loop 1, Alarm 1 output
0 : Network only
1 : Control output 1
2 : Control output 2
3 : Control output 3
4 : Control output 4
0
+334
Loop 1, Alarm 2 output
+342
Loop 1, Alarm 3 output
+582
Loop 2, Alarm 1 output
+590
Loop 2, Alarm 2 output
+598
Loop 2, Alarm 3 output