CONTROL CYCLE
Specify duty cycle for duty ratio output. Disregarded with DC signal output setting.
ADDRESS
PARAMETER
RANGE
DEFAULT
+1281
Control output 1, Control cycle
1.0 to 99.9 seconds
2.0
+1441
Control output 2, Control cycle
+1601
Control output 3, Control cycle
+1761
Control output 4, Control cycle
■
MINIMUM ON/OFF WIDTH
Specify the minimum pulse width for ON and OFF with duty ratio output.
For example, with 1% setting, the output below 1% is output as 0%, while the output above 99% is output as 100%.
ADDRESS
PARAMETER
RANGE
DEFAULT
+1282
Control output 1, Minimum ON/OFF width
0.0 to 50.0 %
0.0
+1442
Control output 2, Minimum ON/OFF width
+1602
Control output 3, Minimum ON/OFF width
+1762
Control output 4, Minimum ON/OFF width
■
OUTPUT SCALING 0% / OUTPUT SCALING 100%
Scales and outputs the assigned output value.
ADDRESS
PARAMETER
RANGE
DEFAULT
+1283
Control output 1, Output scaling 0% *
4
-3200.0 to +3200.0
(Input 1 decimal digits unit or
Input 2 decimal digits unit) *5
0.0
+1284
Control output 1, Output scaling 100% *
4
100.0
+1443
Control output 2, Output scaling 0% *
4
0.0
+1444
Control output 2, Output scaling 100% *
4
100.0
+1603
Control output 3, Output scaling 0% *
4
0.0
+1604
Control output 3, Output scaling 100% *
4
100.0
+1763
Control output 4, Output scaling 0% *
4
0.0
+1764
Control output 4, Output scaling 100% *
4
100.0
*4. Output scaling 0 to 100% is valid only when control output is assigned to PV, Internal SP, Local SP or Remote SP on setting
“OUTPUT ASSIGNMENT”. Disregarded if it is assigned to others.
Output scaling 0% of control output 1 is PV (input value) or SP (target value) at which the control output 1 output becomes 0%.
Output scaling 100% of control output 1 is PV (input value) or SP (target value) at which the control output 1 output becomes
100%.
The same applies to control output 2, control output 3, control output 4.
e.g. If the “OUTPUT ASSIGNMENT” setting is “Loop 1 PV”, as it follows.
If output scaling 0% of control output 1 become 20,
at that time PV of Loop 1 is 20, control output 1 outputs 0%.
If output scaling 100% of control output 1 become 80,
at that time PV of Loop 1 is 80, control output 1 outputs 100%.
*5. Refer to the “DECIMAL” about digits setting
■
OUTPUT 0% / OUTPUT 100%
When output control is 0%, output 0% is setting the value of output from the terminal block of unit.
When output control is 100%, output 100% is setting the value of output from the terminal block of unit.
ADDRESS
PARAMETER
RANGE
DEFAULT
+1285
Control output 1, Output 0%
0.0 to 100.0
*6
+1286
Control output 1, Output 100%
+1445
Control output 2, Output 0%
+1446
Control output 2, Output 100%
+1605
Control output 3, Output 0%
0.0 to 100.0%
0.0
+1606
Control output 3, Output 100%
100.0
+1765
Control output 4, Output 0%
0.0
+1766
Control output 4, Output 100%
100.0
*6. Default value and engineering unit depends upon the model number suffix code as in the table below.
MODEL
DEFAULT(OUTPUT 0%)
DEFAULT(OUTPUT 100%)
UNIT
R3-TC2Ax
4.0
20.0
mA
R3-TC2Vx
0.0
10.0
V
R3-TC2Px
0.0
100.0
%