CONTROL OUTPUT
The Controller has four control outputs (control output 1 through 4) which are assigned to control output, alarm output and
other outputs.
Basic output channel configuration is determined by the model number suffix codes as shown below.
Control output 1, Control output 2
R3-TC2Ax
0 − 20mA DC output
R3-TC2Vx
0 − 10V DC output
R3-TC2Px
12V pulse output
Control output 3, Control output 4
Open collector output
Each output channel can be assigned with alarm output (ON/OFF) or with control output (continuous value) as explained in
the table below.
OUTPUT
ON/OFF
CONTINUOUS VALUE
0 − 20mA DC
ON at 100% scaled current; OFF at 0%
scaled current
Scaled output range is converted into a
proportional current range
0 − 10V DC
ON at 100% scaled voltage; OFF at 0%
scaled voltage
Scaled output range is converted into a
proportional voltage range
12V pulse
ON at 12V; OFF at 0V
Scaled output range is converted into a
proportional duty ratio output
Open collector
ON at closed state; OFF at open state
Scaled output range is converted into a
proportional duty ratio output
■
OUTPUT ASSIGNMENT
ADDRESS
PARAMETER
RANGE
DEFAULT
+1280
Control output 1, Output assignment
See the table below.
16
+1440
Control output 2, Output assignment
32
+1600
Control output 3, Output assignment
16
+1760
Control output 4, Output assignment
32
SET VALUE
PARAMETER
TYPE
OUTPUT SCALING DECIMAL
0
Not assigned
---
----
1
Device error
ON/OFF
----
2
Alarm OR
ON/OFF
----
3
Alarm AND
ON/OFF
----
4
Input error, OR for all loops
ON/OFF
----
16
Loop 1, Heating control output
Continuous value
2
17
Loop 1, Cooling control output
Continuous value
2
18
Loop 1, PV
Continuous value
By input 1 decimal setting
19
Loop 1, Internal SP
Continuous value
By input 1 decimal setting
20
Loop 1, Local SP
Continuous value
By input 1 decimal setting
21
Loop 1, Remote SP
Continuous value
By input 1 decimal setting
22
Loop 1, Input error
ON/OFF
----
23
Loop 1, Remote SP input error
ON/OFF
----
32
Loop 2, Heating control output
Continuous value
2
33
Loop 2, Cooling control output
Continuous value
2
34
Loop 2, PV
Continuous value
By input 2 decimal setting
35
Loop 2, Internal SP
Continuous value
By input 2 decimal setting
36
Loop 2, Local SP
Continuous value
By input 2 decimal setting
38
Loop 2, Input error
ON/OFF
---