R3-TC2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8468 Rev.3 P. 17 / 37
■
WIRING
Choose either 2 wires or 3 wires when the input type is set to RTD or resistor.
ADDRESS
PARAMETER
RANGE
DEFAULT
+129
Universal input 1, Wiring
0 : 2 wires
1 : 3 wires
1
+385
Universal input 2, Wiring
■
BURNOUT
Choose burnout function when the input type is set to thermocouple, RTD, resistor or potentiometer.
ADDRESS
PARAMETER
RANGE
DEFAULT
+130
Universal input 1, Burnout
0 : Disable
1 : Enable
1
+386
Universal input 2, Burnout
■
COLD JUNCTION COMPENSATION
Choose cold junction compensation by the cold junction temperature sensor included in the product package for thermocouple
input.
When the setting is disabled, the terminal temperature is assumed to show 0°C so that the measured emf is directly converted
into temperature.
ADDRESS
PARAMETER
RANGE
DEFAULT
+131
Universal input 1, Cold junction compensation
0 : Disable
1 : Enable
1
+387
Universal input 2, Cold junction compensation
■
TEMPERATURE UNIT
Choose temperature unit used for thermocouple or RTD input.
The setting is applied only to the unit, but not to the temperature values such as SP. If you have changed the unit setting, be
sure to check and change all other temperature values.
ADDRESS
PARAMETER
RANGE
DEFAULT
+132
Universal input 1, Temperature unit
0 : degC
1 : degF
0
+388
Universal input 2, Temperature unit
■
INPUT ZERO ADJUSTMENT / INPUT SPAN ADJUSTMENT
Input signals can be finely adjusted.
The following equation is applied to the engineering unit value data.
[Adjusted value] = [input] × [input span adjustment] + [input zero adjustment]
ADDRESS
PARAMETER
RANGE
DEFAULT
+133
Universal input 1, Input zero adjustment
-300.00 to +300.00
(unit as in the table below)
0.00
+389
Universal input 2, Input zero adjustment
+134
Universal input 1, Input span adjustment
0.8500 to 1.1500
1.0000
+390
Universal input 2, Input span adjustment
INPUT TYPE
UNIT
0 − 20mA DC
mA
-1000 − +1000mV DC
mV
-10 − +10V DC
V
Thermocouple
mV
RTD, Resistor
Ω
Potentiometer
%