3.5.3 SLMP device connection setting
Using the SLMP client function of the DL30-G, I/O can be expanded using SLMP devices.
A maximum of 32 SLMP devices can be connected to single DL30-G device.
Set different IP addresses which do not overlap with the address of the DL30-G for the SLMP device (Slave 0
to Slave 31).
■
SLMP-compatible devices that can be connected to the DL30-G
• MELSEC iQ-R Series (Mitsubishi Electric)
• MELSEC iQ-F Series (Mitsubishi Electric)
• MELSEC Q Series (Mitsubishi Electric)
(Tested and verified)
•
R04CPU
•
FX5U-32M
•
Q03UDECPU
■
Connecting CPU modules for SLMP
The DL30-G is connected to SLMP devices by TCP/IP over the Ethernet.
In order that the DL30-G communicates with an SLMP device, register the device on Ethernet Configuration
setting window and set as follows:
Communication data code: Binary
Communication method: SLMP
Protocol: TCP
IP address: IP address specified in the I/O slave setting of the DL30GCFG
Port No.: Port No. specified in the I/O slave setting of the DL30GCFG
NOTES
See the User Manual of each product for the SLMP setting.
When connecting to the DL30-G via WAN, It is strongly recommended to use VPN in terms of
security.
Switching HUB
Slave 0
DL30
MELSEC iQ-R
Series
CPU Module
Slave 1
MELSEC iQ-F
Series
CPU Module
Slave 2
MELSEC Q
Series
CPU Module