316
DL30-G USERS MANUAL EM-8571-G Rev.2
8.2.11 Schedule
Terminology
Item
Description
Schedule output
Controlled using the scheduling function to be output from the DO,
MD, or GDO channel.
Pattern
A set of schedule outputs assigned to a day.
A pattern consists of 8 schedule outputs and up to 64 patterns can
be created.
➔
Schedule unit
A set of patterns to be assigned to a week.
Up to 32 units can be created.
Assign patterns to the days of the week, respectively to realize ON/
OFF operations according to the days of the week.
➔
One-time schedule assignment
Patterns displayed on the Schedule menu (
➔
changed to different patterns only once.
➔
Permanent schedule assignment
Patterns can be changed to different patterns on the specified dates.
This function is useful when a pattern needs to be changed on a
specific date due to a national holiday, etc.
The registered pattern remains until it is deleted.
➔
CAUTION
In a case where different patterns are set for the same day, the setting is applied in the follow-
ing priority order: (high) Permanent schedule assignment > One-time schedule assignment >
Schedule unit setting (low).
Schedule output
• Schedule output is independent of control output and alarm output.
The channel which is ON for schedule output cannot be turned OFF by control output.
When schedule output, control output, and alarm output are set in the same channel, ON outputs are oper-
ated based on the OR logic among the schedule, control, and alarm outputs.
➔
3.6.6 Digital function register (MD)
,
➔
➔
3.6.9 Grouped digital output (GDO)
• Schedule outputs are operated based on the OR logic among ON schedule outputs of the current time and
date (yyyymmddhhmm).
Be aware when changing the time and/or date of the system, or the schedule settings.
• When the output type of the DO or MD channel set for schedule output is set to ON or OFF on the [Output
type maintenance] menu, the schedule output is disabled.
➔
CAUTION
When automatic time correction of the SNTP client function is enabled (
➔
), be sure to set [Sampling adjustment at time correction] as [Enable] so
that schedule output will not be interrupted due to discontinuous time.
➔
>