70
DL30-G USERS MANUAL EM-8571-G Rev.2
(2) Set the [CH setting] as [I/O module] to enable the [Module address] and [CH No.] fields.
Enter the CH value to be assigned.
1. Select
2. Enter
3. Enter
Up to 2 PI channels can be assigned per module.
Module type
Compatible module
CH No.
Module address
CH No. in the card
2 ch module
R30PA2
CH1
N
1
CH2
N
2
(3) Set the parameter items in the table below.
Parameter
Description
Measurement mode
(module)
Set the type of the 32 bit data read from the I/O module.
• Accumulation
The cumulative total is calculated by accumulating the difference between the value at the
start of cumulative totalizing and the value when it is reset, for each sampling duration.
Select 'Accumulation' when using the totalized pulse input module (model: R30PA2).
• Actual value
The retrieved data is recognized as a signed 32 bit integer, and its value is taken as sampling
data.
Filter
Set the filter function. Select from None / Moving average / Delay buffer.
Selectable only for the actual (engineering unit) values.