315
DL30-G USERS MANUAL EM-8571-G Rev.2
8.2.9 FTP client
File transfer by FTP client function is executed as follows.
• Logging data, event logs, and report forms are registered in a transmission queue.
They are sent to the FTP server in order of registering in the queue.
• Maximum 16 sets of data are stored in the queue.
The data exceeded the max. limit is not registered and discarded.
• When a transfer is failed, it is resent after 2 minutes.
Failed file transfers are retried up to 3 times.
Data is discarded after the 3 times of unsuccessful retries.
• The transmission queue is reset when the DL30-G is switched to the maintenance mode.
8.2.10 Mail reporting
Event reports, regular reports and report forms are sent as follows.
• Occurred event reports, regular reports and report forms are registered in a report queue.
Mail is sent in order of registering in the report queue.
• A maximum of 128 reports are stored in the report queue.
The reports exceeding the limit is not registered and discarded.
• When a mail reporting failure is detected, the mail is resent in 30 seconds after the detection.
Retransmission is repeated up to 3 times, and the report is discarded if a reporting failure is detected for the
fourth time.
• The report queue is reset when the DL30-G is switched to the maintenance mode, or by cancelling the mail
report function.