106
DL30-G USERS MANUAL EM-8571-G Rev.2
(2) Configure the following basic parameters and click [OK] to temporarily store the setting.
Parameter
Description
Function
Select a function among: None / Equal / AND / OR / XOR / NOT / RUN.
RUN: MD turns on when the DL30-G is started up.
Input
Set parameters required for the selected function.
Consecutive: 3 or more consecutive channels can be used for AND and OR operation.
Check [Enable] and specify the top channel in [Type] and [Start CH], and the number of channels
in [Count].
For example, for OR operation for “3” points starting at “DI001," set as follows.
[Type]: DI
[Start CH]: 001
[Count]: 3
When [Function] is set as [Enabled], 'Self-reset timer' (0 to 999 sec.) can be set in the [K1] field of
[Exponent].
Set '0' to disable the 'Self-reset timer'.
The timer starts when the Self-reset timer MD detects OFF-ON operation and stops when the set
time period has elapsed and the Self-reset timer MD turns ON and OFF.
The timer also stops when the Self-reset timer MD is turned OFF while in operation.
CH name
Set a channel name using up to 16 characters.
CH comment
Set a description for the channel using up to 16 characters with the tag name, etc.
Memory at power
loss
Select whether to hold a value immediately before the unit stops due to power failure or reset of
the unit. The held value is output when the unit is restarted.
This parameter is available for MD128 to MD159 only and when the [Function] is disabled.
MD setting