111
DL30-G USERS MANUAL EM-8571-G Rev.2
Resetting PI totalized value (MD)
The cumulative total value of a specific PI can be reset by detecting a rising edge of MD.
The PI channel to be operated needs to be assigned in advance.
➔
(1) Click [Reset totalized value (PI)] button in the [MD setting] window to display the [Reset totalized value
(PI)].
(2) Double-click PI channel to be operated and set as Disable / Enable.
(3) Click [Back] to return to the [MD setting] window.
MD setting
Click
Click
1. Double-click
2. Select
4. Click
3. Click
Reset totalized value (PI)