127
DL30-G USERS MANUAL EM-8571-G Rev.2
The DO channels are used for the control output, alarm output, I/O mapping output, and schedule output.
The I/O mapping output has priority against other types of outputs if more than one function is assigned to a
single channel.
For those no I/O mapping output is assigned, the outputs are handled by OR logic of the control, alarm, and
schedule outputs.
DO
OR
Control Output
(valid at control edge)
• Control on the browser view
• Control by Modbus/TCP slave function
• E-mail delivery success
• E-mail delivery failure
• FTP client communication failure
Scheduled Output
(valid according to preset time)
• Scheduling function
Alarm Output
(valid by communication status or signal level)
• Modbus/TCP master, node communication error
• FTP client, slave communication error
• AI/PI/MA zone limit alarm