154
DL30-G USERS MANUAL EM-8571-G Rev.2
Report form contents setting
(1) Click [Pen information] button to display the [Pen information] window.
Double-click a row of the PEN to be set to display the [Pen information setting] window.
Set relevant parameters by referring to the table below.
Parameter
Description
Type
Choose the signal type among: None / AI / PI / MA.
CH
Choose the channel number.
Sampling method
Choose the data sampling method for hourly data among: Momentary value / Average value /
Peak value (max.) / Peak value (min.).
*
1
Basic data
Choose the operating function for obtaining 'daily data' to be recorded in a Monthly report from
the Daily report data and 'monthly data' to be recorded in a Yearly report from the Monthly
report data among: Sum / Average / Maximum / Minimum.
Data range
• Mode
Choose [Enable] when a specific valid data range is set.
• Upper limit
Specify the upper limit of the data.
• Lower limit
Specify the lower limit of the data.
Error mode
• Mode
A pre-defined value can be applied in the Report form when the DL30-G
is unable to acquire data or when the data is out of the specified range.
Choose among: Previous value / Fixed value / Fixed characters.
• Fixed value
Specify a numeric value for the [Fixed value] mode.
• Fixed characters
Specify characters for the [Fixed characters] mode. (max. 8 characters)
Pen information
Report form
1. Click
Pen information setting
2. Double-click