Operational Tests
Office Alarm Test
5 - 8
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................
Step 15
Press the
ACO
pushbutton on the SYSCTL.
Requirement:
Activated office alarm:
MJ
visual.
The MJ audible alarm should clear.
............................................................................................................................................................................
Step 16
Unseat the second circuit pack from the same function group pair as the
circuit pack removed in Step 12.
Result:
Activated office alarms:
CR
visual, CR audible.
............................................................................................................................................................................
Step 17
Press the
ACO
pushbutton on the SYSCTL.
Result:
Activated office alarm:
CR
visual.
The CR audible alarm should clear.
............................................................................................................................................................................
Step 18
Reconnect the optical fiber jumper removed in Step 14 and reseat the
pair of function units.
Result:
After a few minutes, all alarm indications should clear.
............................................................................................................................................................................
Step 19
Disconnect the office alarm cable connected in Step 1 for the remainder
of the test procedures in this chapter.
Important!
Do NOT delete the cross connect that was entered for
this test.
............................................................................................................................................................................
Step 20
Check off the appropriate box in Appendix E, Installation Checklist.
...........................................................................................................................................................................
End of Steps