Installation Tests
Local Equipment and Cross-connect Tests
...........................................................................................................................................................................................................................................................
4 - 9
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................................................................................................
Local Equipment and Cross-connect Tests
Description
The tests in this section verify the proper operation of the circuit packs
and the circuit pack positions in the Metropolis
®
DMXtend shelf. It
verifies proper cabling from the Metropolis
®
DMXtend to the DSX
cross-connect panel or connecting equipment. The shelf must
successfully pass this test before testing any other feature of the
Metropolis
®
DMXtend.
It is assumed that Chapter 2, Powering and Initial Circuit Pack
Installation for Metropolis® DMXtend Shelf Horizontal Bay Mount is
complete and the Metropolis
®
DMXtend shelf has fiber loopback
cables on the Main OLIUs, with Far-End Communication disabled and
synchronization set to free-running.
On initial installation/turn-up of Metropolis
®
DMXtend there are no
default cross-connects.All cross-connects need to be entered for these
tests. Upon completion of this test all cross-connections will be deleted.
Important!
If the shelf is not fully equipped, move circuit packs
around and repeat the test. Test all circuit pack positions which have
DSX cabling.
Important!
After completing this test, isolate and correct any
incorrect wiring or isolate and replace any failed units. If any
cabling is corrected or units replaced, repeat the Local Equipment
and cross-connect tests until the units pass without failures.
CAUTION
...........................................................................................................................................................................
A properly grounded ESD wrist strap MUST be worn when
handling circuit packs.
WARNING
Unterminated optical connectors may emit laser radiation. Do
not view beam with optical instruments.