Powering and Initial Circuit Pack Installation for
Metropolis
®
DMXtend Shelf Horizontal Bay Mount
Powering
2 - 4
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
Figure 2-1
Power Connections on Metropolis
®
DMXtend
Backplane
............................................................................................................................................................................
Step 4
If fuses are being used, install 15-ampere fuses in the battery
distribution fuse board (BDFB) that powers the Metropolis
®
DMXtend
A and B feeders.
............................................................................................................................................................................
Step 5
If breakers are being used, verify that 15-ampere breakers are installed
and switch the breakers to the ON position for the Metropolis
®
DMXtend A and B feeders.
............................................................................................................................................................................
Step 6
At the Metropolis
®
DMXtend power cable connector, use a voltmeter
and measure the voltage on the power cable between BAT A and BAT
A RTN. Then measure the voltage between BAT B and BAT B RTN.
Requirement:
The voltage MUST be between -40.00 and -60.0 V
DC.
Designation
Color of
Power Cable
Color of Internal
Shelf cable
Position on power cable connector
facing connector with clip release
up
BAT A
Red
Red
Right
BAT A RTN
Red/Black
Left
BAT B
Blue
Red
Right
BAT B RTN
Red/Black
Left
PWR B
PWR A