![LU-VE FSC 4/1 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/lu-ve/fsc-4-1/fsc-4-1_installation-manual_1945542014.webp)
V1
Aux.power supply
22 V (+10/-20%) max. 25mA
Config. 0M
V2
Aux.power supply
22 V (+10/-20%) max. 25mA
Standard
+ 10 V
Aux.power supply
10,0 V (±1%)
OUT
Output signal for Power unit : 0-10V o PWM (Max 5 modules)
V1
Aux.power supply
22V (+10/-20%) max. 25mA
Config.
0X
V2
Aux.power supply
22 V (+10/-20%) max. 25mA
+ 10 V
Aux.power supply
10,0 V (±1%)
OUTPUT SIGNALS
OUT
Output signal for Power unit : 0-10V o PWM (Max 5 modules)
V1
Aux.power supply
5,0 V (±1%)
Su richiesta
Config.
0V
V2
Aux.power supply
5,0 V (±1%)
+ 10 V
Aux.power supply
10,0 V (±1%)
OUT
Output signal for Power unit : 0-10V o PWM (Max 5 modules)
V1
Aux.power supply
22 V (+10/-20%) max. 25mA
Config.
0B
V2
Aux.power supply
5,0 V (±1%)
+ 10 V
Aux.power supply
10,0 V (±1%)
OUT
Output signal for Power unit : 0-10V o PWM (Max 5 modules)
PROTECTION
EMC integrated mains filter
According to EN 55011 (CEI 110-6) Category B : appliances directly connected to low voltage
power mains.
SURGE arrester protection
According to EN 61000-4-5 :Overvoltage category II (4 KV)
Materials
GW-Plast 120 °C
(max. 120 °C) and aluminium
Protection Degree
IP 55
CASEMENT
IP 00
( on request )
Heatsink temperature
60 °C
Environmental pollution
Low pollution
Fire Resistance Category
Category
D
Insulating parts Electric stress
Long time
INSULATION
Casement
Class
I
( use of the protection cable connected to the ground )
2000 Vac
between protection grounding and energized parts of the device
Control circuit
2500Vac
between the driving input and energised parts of the device
4000V
between the driving input and the parts having the supply voltage
Working temperature
-20 T 50
( da –20 °C a + 50 °C )
ENVIROMENTAL
Storing temperature
-30 T 85
( da –30 °C a + 85 °C )
CONDITIONS
Vibrations Lower
Lower of
1G ( 9.8 m/s2 )
Caratteristica di Invecchiamento
60.000 h
INSTALLATION
Wall mounted-only in vertical position with
N
°
4
holes Ø
5
mm,free space above and below the regulator about
100 mm
ENGLISH
14
sequel ...
SCU Technical Characteristics
Mod. / Type
Amp
kg
SCU 08
08
1,4
SCU 12
12
1,5
SCU 16
16
1,7
SCU 20
20
1,8
Ø 5
162
162
145
97
195
SCU 08
SCU 12
M25
Ø min. 8
Ø max. 14
IP 68
Ø 5
210
152
93
240
115
195
SCU 16
SCU 20
M25
Ø min. 8
Ø max. 14
IP 68
The device is suitable for the installation in units of class I, II, III.
=
STANDARD LU-VE
Abcdefg