ADDING A VIRTUAL DEVICE (CONTINUED)
The
[Set device params]
window permits you to change these parameters:
The
Save
option when preceded by an arrow, permits you to save the child device
’
s virtual profile:
Type
The type of the device that has to be added (detector, call point...).
See appendix B at the end of the manual.
Subtype
The specific type of device: if
Type
is a
Detector
, the subtype can be, for example,
Optical
.
See appendix B at the end of the manual.
UUID
Indicates the specific unique identifier of the device.
If you will be linking a single device
“
by switch
”,
specifying this value is not necessary.
If you are linking through
“
wake up
”,
this value is mandatory.
Loop address
This value is automatically assigned to the virtual device according to the analogue address of the
FI750/RF/W2W
(this
is normally 1); nevertheless you can specify another address, as required.
Values span from 2 to 240.
LED Communication
Child device
’
s LED blinks every time there is a communication with its parent network device.
With
Yes
this feature is enabled. With
No
this feature is disabled.
Take into account that LED activity runs out the child device
’
s batteries and you will need to change them more
often.
LED Fault
Child device
’
s LED switches on in case of a fault.
With
Yes
this feature is enabled. With
No
this feature is disabled.
Take into account that LED activity runs out the child device
’
s batteries and you will need to change them more
often.
Even if this feature is disabled, fault messages will be routed to the control panel just the same.
Opt. Ch. Sens.
Used only for optical detectors.
You can set here the alarm sensitivity level for environmental smoke detection.
Can be
High
,
Medium
or
Low
.
Output Ch. En.
Used only for output modules.
You can enable or disable here the 12V / 24V output channel.
With
Yes
this channel is enabled, otherwise
No
disables it.
Out. Supervised
Used only for output modules.
Enables or disables the supervision on the 12V / 24V output channel.
With
Yes
the supervision feature is enabled, otherwise
No
disables it.
If supervision is enabled, short / open events are signalled to the control panel.
Out. Voltage
Used only for output modules.
Using this option you can set the voltage of the 12V / 24V output channel.
12V
for 12 volts or
24V
for 24 volts.
Relay Ch. En.
Used only for output modules.
Here you can enable or disable the relay output channel.
With
Yes
this channel is enabled, otherwise
No
disables it.
Rel. Supervised
Used only for output modules.
Enables or disables the supervision on the relay output channel.
With
Yes
the supervision feature is enabled, otherwise
No
disables it.
If supervision is enabled, short / open events are signalled to the control panel.
According the device type / subtype you select, the set of
personalization options vary.
[Set device params]
Save
Saving
….
You can now link the child device to the system, but if
needed you can postpose this operation.
It is possible for you to modify or delete the recorded
devices; these operations are described in this manual.
12