ADDING A VIRTUAL DEVICE (CONTINUED)

 

 

The 

[Set device params]

 window permits you to change these parameters:

 

 

 

The 

Save

 option when preceded by an arrow, permits you to save the child device

s virtual profile:

 

Type

 

The type of the device that has to be added (detector, call point...).

 

See appendix B at the end of the manual.

 

Subtype

 

The specific type of device: if 

Type

 is a 

Detector

, the subtype can be, for example, 

Optical

.

 

See appendix B at the end of the manual.

 

UUID

 

Indicates the specific unique identifier of the device.

 

If you will be linking a single device 

by switch

”, 

specifying this value is not necessary.

 

If you are linking through 

wake up

”, 

this value is mandatory.

 

Loop address

 

This value is automatically assigned to the virtual device according to the analogue address of the 

FI750/RF/W2W

(this

is normally 1); nevertheless you can specify another address, as required.

 

Values span from 2 to 240.

 

LED Communication

 

Child device

s LED blinks every time there is a communication with its parent network device.

 

With 

Yes

 this feature is enabled. With 

No

 this feature is disabled.

 

Take into account that LED activity runs out the child device

s batteries and you will need to change them more 

often.

 

LED Fault

 

Child device

s LED switches on in case of a fault.

 

With 

Yes

 this feature is enabled. With 

No

 this feature is disabled.

 

Take into account that LED activity runs out the child device

s batteries and you will need to change them more 

often.

 

Even if this feature is disabled, fault messages will be routed to the control panel just the same.

 

Opt. Ch. Sens.

 

Used only for optical detectors.

 

You can set here the alarm sensitivity level for environmental smoke detection.

 

Can be 

High

Medium

 or 

Low

.

 

Output Ch. En.

 

Used only for output modules.

 

You can enable or disable here the 12V / 24V output channel.

 

With 

Yes

 this channel is enabled, otherwise 

No

 disables it.

 

Out. Supervised

 

Used only for output modules.

 

Enables or disables the supervision on the 12V / 24V output channel.

 

With 

Yes

 the supervision feature is enabled, otherwise 

No

 disables it.

 

If supervision is enabled, short / open events are signalled to the control panel.

 

Out. Voltage

 

Used only for output modules.

 

Using this option you can set the voltage of the 12V / 24V output channel.

 

12V

 for 12 volts or 

24V

 for 24 volts.

 

Relay Ch. En.

 

Used only for output modules.

 

Here you can enable or disable the relay output channel.

 

With 

Yes

 this channel is enabled, otherwise 

No

 disables it.

 

Rel. Supervised

 

Used only for output modules.

 

Enables or disables the supervision on the relay output channel.

 

With 

Yes

 the supervision feature is enabled, otherwise 

No

 disables it.

 

If supervision is enabled, short / open events are signalled to the control panel.

 

According the device type / subtype you select, the set of 

personalization options vary.

 

   [Set device params]

 

         Save

 

Saving

….

 

You can now link the child device to the system, but if 

needed you can postpose this operation.

 

It is possible for you to modify or delete the recorded 

devices; these operations are described in this manual.

 

 

 

 

 

 

 

 

12

 

Содержание FI750/RF/W2W

Страница 1: ...FI750 RF W2W GUIDE TO THE KEYBOARD DISPLAY INTERFACE SYSTEM TAURUS SERIES...

Страница 2: ...devices are limited add FI750 RF WE devices to the system to cover completely the fire protected area Child devices are linked to FI750 RF W2W FI750 RF CWE and FI750 RF WE network devices Purpose of...

Страница 3: ...s a bit more complex but not difficult some actions are added to the things that need to be done Program the global Taurus system s settings on the central node Add virtual expanders into the central...

Страница 4: ...e keyboard display user interface you can link one single child device Link by switch linking mode is triggered directly by the user through the child device s onboard switch One or more child devices...

Страница 5: ...access to the next submenu If editing a value sets the cursor to the right digit Enter Enters into the next submenu Confirms the selected setting Exit Returns to the previous menu TM W2W Indicates th...

Страница 6: ...xtension commands for Taurus systems No the control panel uses the Vega protocol s extension commands for Taurus systems Tone period s Timespan value used for the purpose of synchronizing the output o...

Страница 7: ...them On the other hand if Legacy mode is activated only the FI750 RF W2W device can be fetched using Select by Loop Address Select expander Expander 1 MGGG0000 Children 0 Select loop address Address...

Страница 8: ...ed when input signal is in high impedance Low fault raised when input signal is in a low state Charger fault Battery charger fault Disable no fault check Open fault raised when input signal is in high...

Страница 9: ...evices if any already linked Modification of the field channel pair of the central node makes necessary to link again its child devices if any already linked Notification for further actions follows t...

Страница 10: ...Select by Expander The required network device is searched through its sequential number 1 to 16 Select by Loop Address The required network device is searched through its intelligent loop address If...

Страница 11: ...em Config System Config Device Settings Device Settings Add Device Please enter password 0002 Add Device Select Exp By Num Select by Loop Address Select Exp By Num The required network device is searc...

Страница 12: ...will need to change them more often Even if this feature is disabled fault messages will be routed to the control panel just the same Opt Ch Sens Used only for optical detectors You can set here the...

Страница 13: ...select the network device first through its sequential number 1 to 16 Successively you will have to look for the specific child device you wish to link Select expander Expander 1 MGGG0000 Children 1...

Страница 14: ...45 F 55 25 TM W2W Please enter password 0001 Main Menu System Config System Config Device Settings Device Settings Link Device Link Device Select Exp By Num Select by Loop Address Select Exp By Num Y...

Страница 15: ...part of the system Repeat this procedure for every child device you need to link In wakeup mode you do not need to act on the child device s switch every linking operation Linking 01 01 Link success P...

Страница 16: ...ssively you will have to look for the specific child device you wish to delete Select expander Expander 1 MGGG0000 Children 1 Select exp 1 device Address 1 Detector N0GG0000 Select by Loop Address The...

Страница 17: ...to 16 Successively you will have to look for the specific child device you wish to replace Select expander Expander 1 MGGG0000 Children 1 Select exp 1 device Address 1 Detector N0GG0000 Select by Loo...

Страница 18: ...nu System Config System Config Device Settings Device Settings Replace Device Replace Device Select Exp By Num Select by Loop Address Select Exp By Num You select the network device first through its...

Страница 19: ...he child device has been replaced The use of the child device s switch its power on and troubleshooting procedures are explained on the child device s manual Linking 01 01 Link success Press back to e...

Страница 20: ...nt to add to the system use the Up Down Left and Right keys when you have finished press Enter If the virtual expander is successfully added the following acknowledgment window appears Repeat this pro...

Страница 21: ...s Made the discovery channel selection press Enter It is suggested to select Yes that requires mandatorily a backup route for the wireless messages to and from every single FI750 RF WE and the central...

Страница 22: ...LINKING A REAL EXPANDER AUTOLEARN DISCOVERY CONTINUED Autolearn discovery starts The involved FI750 RF WE devices are now integrated in the Taurus system Starting Sys 037 N 09 45 F 55 25 TM W2W 22...

Страница 23: ...t by Loop Address The required network device is searched through its intelligent loop address If Legacy mode is NOT activated the FI750 RF WE have their own loop address therefore Select by Loop Addr...

Страница 24: ...ddress RF is the expander s sequential number in this case 3 and the sequential number of the child device relative to that expander in this case 1 Detector Optical The device type affected by the eve...

Страница 25: ...e device from the 5 The possible values shown are 75 Link power 75dBm 75 85 85 dBm Link power 75dBm 85 100 100 dBm Link power 85dBm 100 105 Link power 100dBm The value is the translation of the link m...

Страница 26: ...nk fault are signalled to the control panel Substitution attempt of an expander it happens when there is an expander that communicates with the other network devices using the same RF address of anoth...

Страница 27: ...e 4 27 Not used channels 868MHz 19 20 21 22 24 Field channel pairs 868MHz 1 37 2 38 3 39 4 40 5 41 6 42 7 43 8 44 17 53 18 54 55 25 56 26 57 27 58 28 59 29 60 30 61 31 62 32 63 33 64 34 65 35 66 36 Di...

Страница 28: ...37 1 38 2 39 3 40 4 41 5 55 25 56 26 57 27 58 28 59 29 60 30 61 31 62 32 63 33 64 34 65 35 66 36 Network channel pairs 916MHz 45 9 46 10 47 11 48 12 49 13 50 14 51 15 52 16 Not used channels 916Mhz 19...

Страница 29: ...ctor Multicriteria FI750 RF OT Detector Thermal ROR FI750 RF T Detector Thermal HT FI750 RF T Call point Normal FI750 RF MCP Input module Supervised FI750 RF M1IN Sounder Wall SND FI750 RF M SST CWS S...

Страница 30: ...50ms 00001 2 12 French tone AFNOR 554Hz for 100ms then 440Hz for 400ms 00101 2 13 HF Back up interrupted tone 2800Hz for 1s then OFF for 1s 11011 2 14 HF Back up interrupted tone fast 2800Hz for 150ms...

Страница 31: ...hen 440Hz for 400ms 00101 2 13 HF Back up interrupted tone 2800Hz for 1s then OFF for 1s 11011 2 14 HF Back up interrupted tone fast 2800Hz for 150ms then OFF for 150ms 11001 6 15 HF Continuous 2800Hz...

Отзывы: