Learning Protection Features
338
6.3.3 Selecting Low Voltage 2 Fault During Operation
Group Code Name
LCD Display
Setting
Setting
range
Unit
PRT
82
Low voltage trip
decision during
operation
Low Voltage2
0
No
0
–1
1
Yes
If input power is disconnected during inverter operation and internal DC voltage decreases
lower than a certain voltage, the inverter disconnects the output and displays low voltage ‗2
(Low Voltage 2)'.
Even if the voltage increases and goes back to the normal state, unlike a low voltage fault, it
remains in a fault state until the user unlocks the fault state.
6.3.4 Output Block via the Multi-function Terminal
When the multi-function input terminal is set as the output block signal terminal and the
signal is input to the terminal, then the operation stops.
Group Code
Name
LCD Display
Parameter
Setting
Setting
range
Unit
IN
65
–
71
Px terminal
setting options
Px Define(Px: P1
–
P7)
5
BX
0-55
-
Output Block by Multi-function Terminal Setting Details
Code
Description
IN-65
–71 Px
Define
When the operation of the multi-
function input terminal is set to ‗5 (BX)‘ and
is turned on during operation, the inverter blocks the output and ‗BX‘ is
displayed on the keypad display. While ‗BX‘ is displayed on the keypad
screen, the inverter‘s operation information including the operation
frequency and current at the time of the BX signal can be monitored. The
inverter resumes operation when the BX terminal turns off and operation
command is input.
Содержание H100
Страница 14: ......
Страница 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 27: ...Preparing the Installation 13 ...
Страница 47: ...33 Installing the Inverter ...
Страница 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Страница 61: ...47 Installing the Inverter ...
Страница 71: ...Learning to Perform Basic Operations 57 ...
Страница 88: ...Learning to Perform Basic Operations 74 ...
Страница 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Страница 120: ...Learning Basic Features 106 Grou p Cod e Name LCD Display Parameter Setting Setting Range Unit Prev ...
Страница 129: ...115 Learning Basic Features ...
Страница 140: ...Learning Basic Features 126 ...
Страница 148: ...Learning Basic Features 134 ...
Страница 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Страница 183: ...169 Learning Advanced Features ...
Страница 184: ...Learning Advanced Features 170 PID Command Block ...
Страница 185: ...171 Learning Advanced Features PID Feedback Block ...
Страница 186: ...Learning Advanced Features 172 PID Output Block ...
Страница 187: ...173 Learning Advanced Features PID Output Mode Block ...
Страница 197: ...183 Learning Advanced Features ...
Страница 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Страница 202: ...Learning Advanced Features 188 EPID2 Control block ...
Страница 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Страница 244: ...Learning Advanced Features 230 ...
Страница 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Страница 362: ...Learning Protection Features 348 ...
Страница 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Страница 524: ...Table of Functions 510 ...
Страница 533: ...Table of Functions 519 ...
Страница 547: ...533 Troubleshooting ...
Страница 564: ...Technical Specification 550 11 3 External Dimensions IP 20 Type 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 585: ...Technical Specification 571 ...
Страница 594: ...580 ...
Страница 595: ...581 ...
Страница 596: ...582 ...