Learning Advanced Features
278
NOTE
Auto change does not work while the auxiliary motors are operating. Auto change is operated
only when all the auxiliary motors are stopped and if all the conditions set for the auto change
are met. When the inverter stops, all motors stop operating, and the auxiliary motor with the
highest priority becomes the starting auxiliary motor. If the inverter power is turned off then
turned back on, the auxiliary motor set at AP1-43 (Starting Aux) becomes the starting auxiliary
motor.
The following diagrams depict the auto change operation when AP1-55 (Auto Ch Mode) is set to
‗2 (Main),‘ when the inverter operation time exceeds the auto change interval set at AP1-58. If
the inverter operation frequency is below the frequency set at AP1-57, all the auxiliary motors
including the start auxiliary motor are turned off. After the delay time set at AP1-91 (Interlock DT)
elapses, the ‗Main‘ auto change is operated. After the ‗Main‘ auto change, the auxiliary motor
that was turned on after the starting auxiliary motor becomes the main motor.
In the following diagrams, because auxiliary motor #1 is the starting auxiliary motor. Auxiliary
motor #2 becomes the main motor after the auto change. The auxiliary motor on/off operation is
identical to that of Aux Exchange, and the ‗off‘ conditions differ based on the FIFO/FILO
configuration.
Содержание H100
Страница 14: ......
Страница 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 27: ...Preparing the Installation 13 ...
Страница 47: ...33 Installing the Inverter ...
Страница 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Страница 61: ...47 Installing the Inverter ...
Страница 71: ...Learning to Perform Basic Operations 57 ...
Страница 88: ...Learning to Perform Basic Operations 74 ...
Страница 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Страница 120: ...Learning Basic Features 106 Grou p Cod e Name LCD Display Parameter Setting Setting Range Unit Prev ...
Страница 129: ...115 Learning Basic Features ...
Страница 140: ...Learning Basic Features 126 ...
Страница 148: ...Learning Basic Features 134 ...
Страница 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Страница 183: ...169 Learning Advanced Features ...
Страница 184: ...Learning Advanced Features 170 PID Command Block ...
Страница 185: ...171 Learning Advanced Features PID Feedback Block ...
Страница 186: ...Learning Advanced Features 172 PID Output Block ...
Страница 187: ...173 Learning Advanced Features PID Output Mode Block ...
Страница 197: ...183 Learning Advanced Features ...
Страница 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Страница 202: ...Learning Advanced Features 188 EPID2 Control block ...
Страница 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Страница 244: ...Learning Advanced Features 230 ...
Страница 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Страница 362: ...Learning Protection Features 348 ...
Страница 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Страница 524: ...Table of Functions 510 ...
Страница 533: ...Table of Functions 519 ...
Страница 547: ...533 Troubleshooting ...
Страница 564: ...Technical Specification 550 11 3 External Dimensions IP 20 Type 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 585: ...Technical Specification 571 ...
Страница 594: ...580 ...
Страница 595: ...581 ...
Страница 596: ...582 ...